Description
2.8 Communication and system connection
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
167
Connection list
number
freely
configurable)
The Modbus TCP port should be blocked in the
gateway to another network if no Modbus TCP
connection to the 3WA from this network is required.
Required for time synchronization via SNTP (Simple
Network Time Protocol)
Necessary for operation of the PROFINET IO interface.
commissioning
Connections are used by the SENTRON powerconfig
configuration software and powermanager for
commissioning the COM190.
When transitioning to another network (e.g. in a router
firewall), these connections should be blocked.
Mapper
Necessary for operation of the PROFINET IO interface.
2.8.3.7 Resetting to factory settings
The following options are available to reset the COM190 communications module to
factory settings:
• Function button S1
• PROFINET standard functions
resetting to the factory settings, all communication parameters and security settings
are reset. The COM190 communications module must then be re
-parameterized in the
same way as for first commissioning.