Description   
2.3 Protection system 
  3WA1 air circuit breaker 
50  Equipment Manual, 02/2023, 92310000002-06 
2.3.5  Description of the protective functions 
2.3.5.1  General description 
Depending on the electronic trip unit and the options selected, the following protective 
functions are available: 
•  Long time LT 
•  Short time ST 
•  Instantaneous short-circuit protection INST 
•  Neutral protection N 
•  Ground-fault alarm 
•  Ground-fault protection GF 
•  Ground-fault protection GF Hi-Z 
•  Directional short time dST 
•  Reverse power protection RP 
•  Enhanced protective functions EPF 
For the ETU600 electronic trip unit, all of the protective functions can generally be set to 
the "closed, ON" or "open, OFF" operating modes. 
In the appendix Device numbers according to IEEE standard C37.2 (Page 562), the 
device numbers (ANSI code) assigned according to IEEE standard C37.2 are given. 
2.3.5.2  Long time LT 
The overload protection is current-dependent and long-time delayed. It is based on the 
rms value of the current and protects cables, busbars and busway systems in the event 
of overload.  
The overload protection is implemented independently for each phase and is equipped 
with a thermal memory. This stores the circuit breaker's thermal state as determined by 
the operational current and shortens the tripping time when reclosing following a trip. 
The overload protection delay is defined at 6 times the current setting I
r
. The minimum 
tripping time is limited to 500 ms.