EasyManua.ls Logo

Siemens SENTRON 3WA1 - Safety Clearances; 3 WA - Size 1

Siemens SENTRON 3WA1
576 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
6.2 Dimension drawings
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
475
6.2.4 Safety clearances
6.2.4.1 3WA - size 1
Fixed-mounted
(1)
Horizontal clearance
(2)
Depth clearance
(3)
Vertical clearance
Breaking
capacity
Rated
voltage
U
e
/ Max. U
e
[V]
Vertical clearance (3)
[mm]
Horizontal
clearance (1)
[mm]
Depth
clearance
(2)
[mm]
Closed
panels
Struts / grids /
perforated sheets
N, S
500 / 525
515
460
0
0
690 / 725
515
460
0
0
M
690 / 725
515
510
0
0
E
690 / 725
560
560
0
0
1000 / 1050
615
615
0
0
IT system only
N, S, M
500 / 525
550
550
0
0
E
690 / 725
615
615
0
0

Table of Contents