Accessories
4.7 Conversion kit for withdrawable circuit breakers and rating coding of the guide frame
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
301
4.7 Conversion kit for withdrawable circuit breakers and rating
coding of the guide frame
4.7.1 Conversion kit for converting fixed-mounted circuit breakers/non-
automatic circuit breakers into withdrawable circuit breakers
4.7.1.1 Description
The conversion kit can be used for converting fixed-mounted circuit breakers into
withdrawable circuit breakers.
The conversion is performed on site by the customer.
The conversion kit which must be ordered for this purpose comprises:
Complete racking mechanism
Racking shaft
Control gate
Shorter circuit breaker feet for withdrawable circuit breakers
Coding pins for withdrawable breaker and guide frame for rated-current coding
WARNING
Overheating and fire hazard as a result of missing rated-current coding.
An incorrect combination of guide frame and circuit breaker in the guide frame can
result in a lack of contact at the blade contacts, leading to overheating and fire hazard.
Rated-current coding must be installed to ensure that only withdrawable circuit
breakers with the appropriate blade contacts can be used in the guide frames.