Description 
  2.5 Electronic trip unit ETU600 
3WA1 air circuit breaker 
Equipment Manual, 02/2023, 92310000002-06 
91 
2.5.2.4  Rotary switch 
The electronic trip unit ETU600 has five rotary switches for parameterizing the basic 
protective functions. 
 
 
When the circuit breaker is delivered, the 
factory basic settings for the position "e.SET" 
are:
 
  I
r
: 0.4 x I
n
 
  t
r
: 0.5 s 
  I
sd
: 0.6 x I
n
 
  t
sd
: 0.1 s 
  I
i
 1.5 x I
n
 
Nine fixed values can be set mechanically for each rotary switch. The tenth position is 
marked with "e.SET". In this position, the parameter can be set using the operating keys 
on the display or with the help of the SENTRON powerconfig configuration software via 
Bluetooth or communication. 
2.5.2.5  Voltage tap module 
A voltage tap module VTM is required for measuring the voltage and calculating further 
metering values. It is available as an option for 3WA circuit breakers with rated voltage 
up to 1000 V and ETU600. 
The voltage tap module is available in two versions: 
•  VTM680 voltage tap module 
For 3WA circuit breakers with breaking capacity N, S, M, H, C and maximum rated 
voltage 690 V AC 
•  VTM640 voltage tap module 
For 3WA circuit breakers with breaking capacity E and max. rated voltage 1000 V AC 
Note 
Breaking capacity E and internal voltage tap
 
breakers with breaking capacity E and an internal voltage tap for metering 
-I to PMF-III, the rated insulation voltage voltage U
i
 and the rated 
 voltage U
e
 are reduced to 1000 V AC. 
It is not possible to use this combination
 with a line voltage of 1150 V AC.