Description 
  2.10 Zone-selective interlocking ZSI 
3WA1 air circuit breaker 
Equipment Manual, 02/2023, 92310000002-06 
189 
2.10.3  Monitoring and ZSI test function 
Monitoring function 
When the external voltage supply (24 V DC) is activated, any existing module on the 
CubicleBUS² is automatically registered. The ETU600 electronic trip unit then 
permanently monitors the presence of the registered modules and reports an error if a 
registered module is no longer detected.  
For the ZSI200 module, a nonvolatile test can be activated that checks whether the 
module is present as the ETU600 is starting. In this case, the ETU600 checks during its 
activation whether a ZSI200 module is present on the CubicleBUS
2
. If the ZSI200 module 
is not detected when the ETU600 is activated, this is reported as an error. 
The ZSI200 module monitors the ZSI control lines for short-circuits.  
Detected errors are signaled, see Chapter Display of errors and alarms (Page 181). 
Test function 
The wiring of the ZSI system can be checked with the "ZSI Test" function on the 
ETU600.  
This test function can be used to send a permanent control signal at the ZSI interfaces 
port A and port B and to check the reception of a control signal. 
2.10.4  Parameterization 
The settings for the ZSI system required for the circuit breaker can be set via the display 
and the operating keys of the ETU600, or with the help of the SENTRON powerconfig 
configuration software via Bluetooth or communication.  
For the ZSI function, the delays t
ZSI
 and the sending as well as receiving of the control 
signal must be parameterized. 
The following settings are possible: 
 
 
 
Evaluates an incoming control signal for the short-time-delayed short-
circuit protection ST (can be switched on/off) 
When the short-time-delayed short-circuit protection ST is triggered, a 
control signal is sent (can be switched on/off) 
ZSI
ZSI
 for short-time-delayed short-circuit protection ST 
Setting range 0.04 s … 0.4 s 
Evaluates an incoming control signal for the ground-fault protection GF 
(can be switched on/off) 
When the ground-fault protection GF is triggered, a control signal is sent 
(can be switched on/off) 
ZSI
ZSI
 for ground-fault protection GF 
Setting range 0.04 s … 0.4 s 
Monitoring of the ZSI200 module in the startup phase (can be switched 
on/off) 
Switching monitoring on and off is only possible via the SENTRON 
powerconfig configuration software.