Accessories   
4.9 Interlocking 
  3WA1 air circuit breaker 
332  Equipment Manual, 02/2023, 92310000002-06 
4.9.2  Interlocking of two circuit breakers using a Bowden cable 
 
Possible circuit breaker statuses 
 
Description 
In the case of a line infeed via transformer and a generator infeed, a circuit breaker can 
only ever be closed when the other one is open. Power is provided either by the normal 
power supply (circuit breaker Q1) or the standby power supply (circuit breaker Q2). 
Required materials 
An interlocking module with a Bowden cable is required for each circuit breaker, i.e. two 
mechanical interlocks must be ordered. 
Connections of the Bowden cables