Troubleshooting 
  8.2 Troubleshooting for the ETU600 electronic trip unit 
3WA1 air circuit breaker 
Equipment Manual, 02/2023, 92310000002-06 
543 
8.2  Troubleshooting for the ETU600 electronic trip unit 
 
ACT LED does not flash when the 
main contacts are closed. 
Electronic trip unit is not activated; 
the operational current via the main 
contacts is too low. 
An external power supply is required 
for activating the electronic trip unit 
below the activation limit. 
Internal self-test cannot be started. 
ACT LED flashes; the display is dark. 
The ambient temperature is outside 
the range -25 °C to 60 °C. 
Implement suitable measures to 
change the ambient temperature. 
The operational current is close to the 
activation limit of the ETU within a 
narrow range. The protective function 
is already supplied with power, but 
not the display; see Chapter 
Activation limits and power supply 
(Page 
76). 
The display is automatically activated 
when the load is greater.  
If this occurs frequently: Connect the 
ETU600 to an external 24 V DC power 
supply. 
No tripping during internal self-test 
with tripping operation. 
 
The main contacts of the circuit 
breaker are not closed. 
Tripping solenoid F5 is defective. 
Connection between electronic trip 
unit and SENTRON powerconfig 
configuration software cannot be 
made via the USB-C interface or 
Bluetooth. 
 
Bluetooth and USB-C interface 
TUI600 is defective. 
Replace the ETU including the TUI600 
module. 
The TUI600 module is not active 
because of low energy (only for ETU 
with its own power supply) 
Check power supply of the ETU600. 
USB-A to USB-C connecting cable is 
used. 
USB-C to USB-C connecting cable is 
used. 
Write protection cannot be removed. 
PIN code for write protection has 
been lost. 
powerconfig configuration software: 
1.  Connect powerconfig via USB-C. 
2.  Call up the menu 
"Device > Reset > ETU600 passw
ord" menu. 
 
 
Fault  Indication on the 
Cause  Remedy 
Circuit breaker trips and INFO LED 
lights up red. 
contact Service 
processor 
trip unit. 
Service 
analog measuring circuit 
ETU Error, option plug, 
contact Service 
replace the option plug 
approved or missing 
specifications of the 
option plug and replace 
if necessary.