Integration in power distribution equipment
7.3 Derating in the power distribution equipment
3WA1 air circuit breaker
524 Equipment Manual, 02/2023, 92310000002-06
7.3.4 Derating 3WA13
The following tables show the derating for size 3, installed in a control panel.
Fixed-mounted, IP31/IP41 - ventilated
Control panel dimensions H x W x D [mm]: 2200 x 1000 x 800
Rated
current
Conductor cross-
section
Number
of 3WAs
Max. operational current at ambient temperature
10 mm
10 mm
Fixed-mounted, IP55
Control panel dimensions H x W x D [mm]: 2200 x 1000 x 800
Rated
current
Conductor cross-
section
Number
of 3WAs
Max. operational current at ambient temperature
10 mm
10 mm