EasyManua.ls Logo

Siemens SENTRON 3WA1 - Minimum Cross-Sections of Main Conductors for DC; Size 3; Basic Data

Siemens SENTRON 3WA1
576 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
6.3 Technical specifications of 3WA circuit breakers
3WA1 air circuit breaker
502 Equipment Manual, 02/2023, 92310000002-06
6.3.3.9 Minimum cross-sections of main conductors for DC
3WA12
DC
1000 A
2000 A
4000 A
Minimum cross-sections of main conductors
Copper bars, bare or painted black
1 x 50 x 10 mm
2 x 50 x 10 mm
On the infeed and
outgoing sides:
3 x 100 x 10 mm
For jumpers:
6 x 250 x 5 mm
6.3.4 Size 3
6.3.4.1 Basic data
3WA13
AC
Fixed-mounted
Withdrawable
Key electrical data
Rated operational voltage U
e
V
1150 at 50/60 Hz
1150 at 50/60 Hz
Rated insulation voltage U
i
V
≤ 1150
≤ 1150
Rated current
A
4000 … 6300
4000 … 6300
Size
3
3
Weight
Circuit
breaker
3-pole /
4-pole
4000 A
kg
82 / 99
88 / 106
5000 A
kg
82 / 99
88 / 106
6300 A
kg
90 / 108
96 / 108
Guide
frame
3-pole /
4-pole
4000 A
kg
--
60 / 84
5000 A
kg
--
60 / 84
6300 A
kg
--
70 / 119
You will find basic data that are identical for all sizes in Chapter Basic data for sizes 1 to
3 (Page 489).

Table of Contents

Related product manuals