EasyManua.ls Logo

Siemens SENTRON 3WA1 - Page 503

Siemens SENTRON 3WA1
576 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
6.3 Technical specifications of 3WA circuit breakers
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
501
3WA12
DC
Endurance (operating cycles)
Breaking capacity D
Mechanical
Without
maintenance
10000
10000
10000
With
maintenance
4)
20000
20000
20000
Electrical
Without
maintenance
600 V
6000
6000
4000
With
maintenance
4)
20000
20000
20000
Breaking capacity E
Mechanical
Without
maintenance
10000
10000
10000
With
maintenance
4)
20000
20000
20000
Electrical
Without
maintenance
1000 V
1000
1000
1000
With
maintenance
1000 V
4)
2000
2000
2000
Without
maintenance
1500 V
5)
1000
1000
1000
With
maintenance
1500 V
4)
20000
20000
20000
4)
Maintenance means: Replace main contacts and arc chutes (see Chapter Inspection and maintenance
(Page 387))
5)
1500 V DC only with 4-pole non-automatic circuit breakers
Switching frequency
Breaking capacity D
Electrical
3-pole
45 / h
45 / h
45 / h
4-pole
60 / h
60 / h
60 / h
Breaking capacity E
Electrical
3-pole
45 / h
45 / h
45 / h
4-pole
60 / h
60 / h
60 / h

Table of Contents