Description   
2.3 Protection system 
  3WA1 air circuit breaker 
76  Equipment Manual, 02/2023, 92310000002-06 
2.3.8  Activation limits and power supply 
The electronic trip unit does not require auxiliary power. The electronic trip unit is 
powered by the circuit breaker's internal current sensors. Depending on the operational 
current, the electronic trip unit of the circuit breaker is activated from: 
 
pole load 
 
(frequency: 1 Hz) 
Electronic trip unit active  
ETU600: Display off 
 
(frequency: 1 Hz) 
Electronic trip unit active  
ETU600: Display on 
 
(frequency: 1 Hz) 
Electronic trip unit active 
ETU600: Display on 
TUI600: active 
If you use functions with data exchange via the CubicleBUS
2
 with the ETU600 electronic 
trip unit, an external 24 V DC power supply must be connected to the secondary 
disconnect terminals X8-3 and X8-4. This means that the ETU600 is active even when 
the circuit breaker is open or when the operational current is below the activation limit. 
 
WARNING 
Loss of direct-acting circuit breaker functionality with option code Z = K60 
(internal current sensors, without energy cores, for applications with frequency 
converters) 
When the circuit breaker is equipped with current sensors without energy cores, the 
electronic trip unit is not self-powered. 
For these applications, an undervoltage release and an external 24 V DC power supply 
are required for activating the electronic trip unit. 
The auxiliary power supplying the electronic trip unit is internally coupled to the 
undervoltage release of the circuit breaker.