Description 
  2.8 Communication and system connection 
3WA1 air circuit breaker 
Equipment Manual, 02/2023, 92310000002-06 
163 
2.8.3.6  Access protection functions 
Overview 
To restrict access to the communications module or prevent unauthorized access, the 
module offers several access protection functions. These access protection functions are 
implemented both as hardware and software functions and in network security: 
•  Hardware protective functions: 
–  Parameter write protection 
–  Remote Switching Protection 
•  Software protective functions 
–  Modbus TCP whitelist (COM190) 
–  Settable TCP port (COM190) 
–  Signed firmware 
•  Protection of the network infrastructure 
Hardware-based access protection functions 
The COM190 and COM150 communication modules have two hardware access 
protection functions. 
The parameter write protection prevents parameters from being changed and 
unintentional actions from being carried out. It is part of the cybersecurity functions.  
Remote Switching Protection prevents the 3WA circuit breaker from being closed and 
opened via the fieldbus communication connections.