Description
2.8 Communication and system connection
3WA1 air circuit breaker
162 Equipment Manual, 02/2023, 92310000002-06
Smartphone / tablet via Bluetooth interface
To commission a communication module via a smartphone or tablet, proceed as follows:
1. Connect your smartphone/tablet to the Bluetooth interface of the 3WA circuit breaker.
2. Start the SENTRON powerconfig configuration software app.
3. In the SENTRON powerconfig configuration software, drag a 3WA circuit breaker into
the project.
4. Select the Bluetooth interface as gateway.
5. Load the current parameters of the 3WA circuit breaker into the project.
6. Edit the network parameters of the communication module.
7. Load the changed parameters into the 3WA circuit breaker.
The communication module can then be accessed under the set network parameters.
PROFINET commissioning procedures
Requirement
• 3WA circuit breaker with ETU600 electronic trip unit
• COM190 communications module
Note
With two communications modules, one module must be configured for module role A
and the other module for module role B.
• External 24 V DC power supply
• PROFINET master
• Optional SENTRON powerconfig configuration software version 3.17 or higher
• Optional STEP 7 V5.5 or higher, TIA Portal
Procedure
To commission the COM190 communications module via PROFINET, download the
GSDML files for the COM190 from the internet
(https://support.industry.siemens.com/cs/WW/en/view/109793939
).
The GSDML files can be imported in STEP 7 V5.5 or higher, TIA Portal, and other
PROFINET configuration tools.
Note
PROFINET settings made with the SENTRON powerconfig configuration software only
become effective after a restart of the COM190 communications module. A restart of the
communications module can be init
iated by briefly interrupting the 24 V power supply