EasyManua.ls Logo

Siemens SENTRON 3WA1 - Technical Specifications; Part Number

Siemens SENTRON 3WA1
576 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Accessories
4.4 Accessory auxiliary switches and signaling switches
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
273
4.4.5.2 Technical specifications
First trip alarm switch S24
Changeover contact
Second trip alarm switch S25
NO contact
Contact stability from
1 mA at 5 V DC
Rated insulation voltage U
i
250 V DC / 250 V AC 50/60 Hz
Fuse protection of the control circuit
Smallest permissible DIAZED fuse, gL
6 A Dz (quick-response)
Rated operational current I
e
With breaking capacity DC12
24 V
5 A
30 V
2.5 A
48 V
2.5 A
60 V
0.4 A
110 / 127 V
0.4 A
220 / 240 V
0.2 A
With breaking capacity DC13
24 V
2.5 A
30 V
1 A
48 V
1 A
60 V
0.2 A
110 / 127 V
0.2 A
220 / 240 V
0.1 A
With breaking capacity AC12
≤ 240 V AC
6 A
With breaking capacity AC13
110 … 127 V
5 A
220 ... 240 V
4 A
4.4.5.3 Part number
Trip alarm switch
Z-option
Part number
Trip alarm switch S24
--
3WA9111-0AH02
Second trip alarm switch S25
K06
3WA9111-0AH03
You can purchase the accessories in the Siemens Industry Mall
(http://www.siemens.com/product?3WA9111-0AH0*).

Table of Contents