EasyManua.ls Logo

Siemens SENTRON 3WA1 - Page 478

Siemens SENTRON 3WA1
576 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
6.2 Dimension drawings
3WA1 air circuit breaker
476 Equipment Manual, 02/2023, 92310000002-06
Withdrawable circuit breakers
(1)
Horizontal clearance
(2)
Depth clearance
(3)
Vertical clearance
Breaking
capacity
Rated
voltage
U
e
/ Max. U
e
[V]
Vertical clearance (3)
[mm]
Horizontal
clearance (1)
[mm]
Depth
clearance
(2)
[mm]
Closed
panels
Struts /
grids /
perforated
sheets
With arc
chute cover
With arc chute
cover;
against closed
panels
N, S
500 / 525
515
460
461
0
40
0
690 / 725
515
460
461
0
40
0
M
690 / 725
515
510
461
0
40
0
E
690 / 725
560
560
--
1)
0
--
1)
0
1000 / 1050
615
615
0
0
IT system only
N, S, M
500 / 525
550
550
--
1)
0
--
1)
0
E
690 / 725
615
615
0
0
1)
Arc chute cover not permissible

Table of Contents

Related product manuals