L S I G
Alarm / status Measure / comment
Flashing fast
(2 Hz)
Flashing fast
(2 Hz)
Temperature alarm Lower the ambient
temperature or
reduce the continuous
operating current.
On
Pre-alarm L, power
ow is greater than
90% of the threshold
value
On
Circuit breaker has
been tripped by the L
release
Clear faults in the pow‐
er system and close the
circuit breaker again.
On
Circuit breaker has
been tripped by the S
release
Clear faults in the pow‐
er system and close the
circuit breaker again.
On
Circuit breaker has
been tripped by the I re‐
lease
Clear faults in the pow‐
er system and close the
circuit breaker again.
On
Circuit breaker has
been tripped by the G
release
Clear faults in the pow‐
er system and close the
circuit breaker again.
Flashing fast
(2Hz)
Threshold has been ex‐
ceeded, tripping delay
is elapsing
Reduce rated current
(disconnect loads)
Flashing fast
(2Hz) with 2s
pause
Parameter error, rotary
coding switch in wrong
position
Check and correct:
• I
r
< I
sd
or I
sd
< I
i
• I
u
< (2xI
n
xI
r
) if
I
N
=200%
• I
g
> 0.25xI
n
with a
rating plug for
400A;
otherwise
I
g
>0.2xI
n
Flashing fast
(2 Hz)
Installation error Check and correct the
installation.
Operation
6.2Alarms
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Equipment Manual, 10/2023, L1V30499596002-03 193