When the system signal of the photovoltaic inverter and water temperature in the tank is less than
60, heat pump will heat up water until 65.
Note: Photovoltaic cycle can be activated or deactivated on control panel, default is deactivated, refer
to configuring parameters table.
4) Solar pump circulation cycle
When Solar collector temperature30, and solar collector temperaturetank water
temperature +7℃,start the solar pump.
When Solar collector temperature30℃,or solar collector temperature120℃,or solar
collector temperaturetank water temperature +4℃,stop the solar pump. Continuously detect solar
collector temperature and tank water temperature.
Note: Solar pump circulation cycle can be activated or deactivated on control panel, default is
deactivated, refer to configuring parameters table. This function is optional.
5) E-Anode function
The appliance is equipped with a magnesium anode, the E-Anode (impressed current anode) is
optional.
Note: E-Anode function can be activated or deactivated on control panel, default is activated, refer to
configuring parameters table. This function is optional.