81
ES
PT
ENG
3.2 ACCESS TO INSTALLER'S
PARAMETERS
For access to the installer's parameters,
press simultaneously the keys of boiler
panel ( and ) for 5 seconds.
The red LED flashes and the display shows:
The parameters can be scrolled with
or .
To ent er the paramet er press or .
The value set flashes, the display shows:
Proceed as follows to change the set value:
- set the new value using or .
- confirm the set value using or .
Press to exit the parameters section.
The display is shown automatically after 5
minutes.
The parameters section contains the
alarms log, info and meters (display only).
3.2.1 Replacing the board or
RESETTING parameters
If the electronic board is replaced or reset,
it is necessary to configure PAR 01 and
PAR 02 by associating the following values
to each type of boiler to be able to restart
the boiler:
NOTE: the boiler panel has a label with
the values that have to be set for PAR 01
and PAR 02 (fig. 21).
BOILER GAS MODELS PAR 1
METHANE 25 01
BF (G20) 30 02
LPG 25 03
(G30/G31)
30 04
METHANE 25 05
OF (G20) 30 06
LPG 25 07
(G30/G31)
30 08
BOILER PAR 2
OF/BF 09
OF/BF 10
combined
with sun-panel system
OF/BF 13
with automatic filling
OF/BF 14
combined
with sun-panel system
and with automatic filling
PARAMETERS INSTALLER
FAST CONFIGURATION
PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
01 Combustion configuration -- = ND = = “--”
1 ... 8
02 Hydraulic configuration -- = ND = = “--”
1 ... 22
03 Disabling of voltage presence LED 0 = Disabled = = 01
1 = Enabled
04 Correction of external probe values -5 ... 05 °C 1 00
05 Timer block of the keys -- = Disabled Min. 1 15
1 ... 99
D.H.W. - HEATING
PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
10 Boiler antifreeze 0 ... 10 °C 1 03
11 External sensor antifreeze -- = Disabled °C 1 - 2
- 9 ... 05
12 C li m at ic cu r ve se t ti n g 03 .. . 4 0 = 1 2 0
13 Minimum temperature heating 40 ... PAR 14 °C 1 40
14 Maximum temperature heating PAR 13 ... 80 °C 1 80
15 M a xi mu m p o we r h ea ti ng 3 0 . . . 9 9 % 1 9 9
16 Post-circulation time 0 ... 99 10 sec. 1 03
17 Pump heating activation delay 0 ... 99 10 sec. 1 01
18 Re-ignition delay 0 ... 10 Min. 1 03
19 M od u la ti on D .H .W. f low me t e r - - = D is ab le d = = 01
1 = Enabled
29 Anti-legionella (only D.H.W. tank) -- = Disabled °C 1 “--”
50 ... 80
PARAMETERS RE-SET
PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
49 * Reset default parameters -- , 1 = = =
(PAR 01 - PAR 02 equal “---”)
* If the current setting is difficult to understand or anomalous behaviour or if it is difficult to understand
the boiler, it is advised to restore the initial parameter values by setting PAR 49 = 1 and PAR 1 and
PAR 2 as specified in point 3.2.1.
ALARMS (visualization)
PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
A0 Last code anomaly appearance = = = =
A1 Code anomaly previously appearance = = = =
A2 Code anomaly previously appearance = = = =
A3 Code anomaly previously appearance = = = =
A4 Code anomaly previously appearance = = = =
A5 Code anomaly previously appearance = = = =
A6 Code anomaly previously appearance = = = =
A7 Code anomaly previously appearance = = = =
A8 Code anomaly previously appearance = = = =
A9 Code anomaly previously appearance = = = =
INFO (visualization)
PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
i0 External sensor temperature -9 ... 99 °C 1 =
i1 C.H. 1 sensor temperature -9 ... 99 °C 1 =
i2 C.H. 2 sensor temperature -9 ... 99 °C 1 =
i3 D.H.W. sensor temperature -9 ... 99 °C 1 =
i4 Auxiliary sensor AUX temperature -9 ... 99 °C 1 =
i5 Set of effective heating temperature PAR 13 ... PAR 14 °C 1 =
i6 Level survey flame 00 ... 99 % 1 =
i7 Current to the modulator 00 ... 17 10 mA 1 =
i8 Flow rate D.H.W. flow meter 00 ... 99 l/min 1 =
COUNTERS (visualization)
PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
c0 Number hours of operation of the burner 00 ... 99 h x 100
0,1 from 0,0 to 9,9
00
1 from 10 to 99
c1 Number of ignitions of the burner 00 ... 99 x 1000
0,1 from 0,0 to 9,9
00
1 from 10 to 99
c2 Number total of the anomalies 00 ... 99 x 1 1 00
c3
Number approached the parameters installator
00 ... 99 x 1 1 00
c4
Number approached the parameters OEM
00 ... 99 x 1 1 00