ISOLATED THE
THE GROUND IS ASSOCIATED
WlTH ONE OF THE DAUGHTER .
CARDS YOU LAST INSTALLED
DISCONNECT POWER TO THE ET
AS FOLLOWS:
c
l
DISCONNECT
BAlTERlES FIRST.
l
DlSCONhlECT AC
LAST.
TROUBLESHOOT THE CARD’S
ASSOCIATED MONlTOR OR
CONTROL POINT WIRING FOR
GROUNDS AND REPAIR
t
REMOVE HALF OF THE
DAUGHTER CARDS YOU
LAST INSTALLED
REAPPLY POWER TO THE ET
AS FOLILOWS:
3
l
CONIIECT AC FlRST.
l
CONIIECT BATTERIES
LAST.
f
CONNECT YOUR VOM ACROSS
TPS(+)AND
TP6 (OV) OF THE POWER
SUPPLY BOARD AS BEFORE
THE GROUND IS ASSOCIATED
WITH ONE OF THE DAUGHTER
LEVEL GREATER CARDS YOU LAST REMOVED
GROUND FAULT Trouble
FIGURE 5G