TABLE A-l
(continued)
TRANSPONDER NUMBER
SWI-3
SWl-4 SW1 -5
SW1 -6
SW1 -7 SW1 -8
49
ON
50 OFF
51 ON
52 OFF
53 ON
54 OFF
55 ON
56
OFF
57
ON
58 OFF
59 ON
60
OFF
6:
ON
62
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SW2 is used to teli the CDT how many monitor points are present (from zero to 128 possible monitor devices). Set
the switches on SW2 as indicated in Table A-2.
Switches SW3-1 through SW3-7 are used to tell the CDT how many control points are present (from zero to 6:
possible control devices). Set the switches as indicated in Table A-3.
Switch SW3-8 is used to indicate whether the MAPNET’” II is single line or McCulloh loop. Set SW3-8 ON tc
indicate McCulloh loop; set SW3-8 OFF to indicate single line.
CAUTION: At least one monitor must be ON or the CDT panel will not operate.
Jumpers JWl through JW6 are set as indicated below.
JWI and JWZ are IN, and are not normally field-alterable.
JW3 is IN for local mode operation.
JW4 is OUT, and is not normally field-alterable.
JW5 is IN when 2120 communications occur via RS232C interface, and OUT for normal communications.
JW6 is OUT when 2120 communications occur via RS232C interface and IN for normal communications.
13