4
Wiring Note: To prevent Electrostatic Discharge (ESD), use a wrist strap assembly that connects to
ground. Ensure power is OFF before installing or servicing the annunciator.
To properly install the remote annunciator:
1. Terminate the annunciators RUI communication and power lines (Figure 3).
2. Connect the ground harness (see Figure 2) to the metal back box’s Earth ground.
3. Connect the RUI wiring from COMM+ and COMM- on the remote annunciator to RUI
terminal on the 4007ES panel power supply (see Figure 4).
Figure 4. Wiring Diagram
4. Set Jumper P1 on the 4007ES for Class A or Class B wiring.
5. To power the remote annunciator, connect the cable from 24+ and 24- on the 4007ES power
supply to 24V and 24C (0V) on the remote annunciator (Figure 4).
Figure 3. Terminating the COMM and Power Line
TB1-1: 24V IN from FACP Power Supply or
Previous Annunciator
TB1-2: 24V OUT to Next Annunciator
TB1-3: 24C IN from FACP Power Supply or
Previous Annunciator
TB1-4: 24C OUT to Next Annunciator
TB1-5: +COMM IN
+RUI communications from FACP or Previ-
ous Annunciator
TB1-6: +COMM OUT
+RUI communications to Next Annunciator
TB1-7: -COMM IN
-RUI communications from FACP or Previous
Annunciator
TB1-8: -RUI communications to Next
Annunciator
TB1-9: SHIELD IN TB1-10: SHIELD OUT
7 8 9 10
24V
24C (0V)
1 2 3 4 5 6
- COMM
+ COMM
SHIELD
IN OUT
IN OUT IN OUT
IN OUT IN OUT
7 8 9 10
24V
24C (0V)
1 2 3 4 5 6
+COMM
-COMM
SHIELD
IN OUT
IN OUT IN OUT
IN OUT IN OUT
Color Touchscreen
LCD Annunciator
7 8 9 10
24V
24C (0V)
1 2 3 4 5 6
+COMM
-COMM
SHIELD
IN OUT
IN OUT IN OUT
IN OUT IN OUT
RUI
4007ES PSU
B+
B-
A+
A-
Color Touchscreen
LCD Annunciator
24+
24-
AUX Power