Features
Panel mounted modules provides fire alarm
system status using the ASHRAE BACnet
building automation communication protocol
BACnet (Building Automation Control Network)
protocol reference:
Communications are via BACnet IP (internet protocol)
Reference: ANSI/ASHRAE Standard 135
Connections:
To fire alarm system via RS-232 port B, configured
for Computer Port Protocol (see page 3 for model
number reference per panel)
Output port provides Ethernet LAN (local area
network) connection
BACpac Ethernet Module is pre-programmed:
Module is pre-programmed with digital pseudo points
linked to BACnet objects
Up to 1000 status changes (monitor point status) can
be recognized from the fire alarm control panel
Compatible Simplex
®
fire alarm control panels:
4100ES and 4100U Series fire alarm control panels
and Network Display Units (NDU)
4010ES Series fire alarm control panels
Installed legacy Models 4100/4100+ and 4120 Series
fire alarm control panels and NDU (software revision
updating may be required
Listings reference:
UL listed to Standard 864
ULC listed to Standard S527
Description
The BACpac Ethernet module provides a supplementary
communications interface that converts computer terminal
information from a compatible Simplex fire alarm control
panel into the building automation protocol of BACnet.
With this module, status information from the fire alarm
control panel can be provided to other components of the
building automation network with the detail and
information format required.
Providing this information allows other systems to
properly respond to fire alarm system activity in addition
to the primary fire alarm response that is under the control
of the fire alarm control panel.
ALARMFIRE
PULL DOWN
ALARMFIRE
PULL DOWN
LAN Connected BACnet System Controllers
Facility LAN
System
Workstation
Fire Alarm
Network
Fire alarm
initiating devices
Simplex Fire Alarm
Control Panel
Fire Alarm System
ALARM
ALARM
4100-6069 BACpac
Ethernet Module
Facility LAN
Fire Control
FIRE ALARM
CONTROL
DISCONNECT
POWER BEFORE
SERVICING
CAUTION
** SYSTEM I S NO R MAL **
12:02:15pm Mon 8-Mar-99
SUP
V
ACK
SYSTEM
SUPERVISOR
Y
ALARM
ACK
FIRE
ALARM
TROUBLE
ACK
SYSTEMTROUBL
E
ALARM
SILENCE
ALARM
SILENCED
SYSTEMRESE
T
AC
POWER
Typical Building Automation LAN with
Simplex Fire Alarm Control Panel and BACpac Portal
(shown with 4100ES panel for reference)
This document is a summary of the flexibility available
with BACnet communications. Please contact your local
Simplex product supplier for further information
concerning your specific application.
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7165-0026:0251 (4100 Series) or 7165-0026:0369 (4010ES) for allowable values and/or
conditions concerning material presented in this document. It is subject to re-examination,
revision, and possible cancellation. This product was not approved by FM, or accepted by
MEA (NYC) as of document revision date. Additional listings may be applicable; contact
your local Simplex product supplier for the latest status. Listings and approvals under
Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
Fire Control Panels
UL, ULC, CSFM Listed* BACpac
Ethernet Portal Modules
Model 4100-6069 and 4010-9915
S4100-0051-3 9/2012
Question and Answer IconNeed help?

Do you have a question about the Simplex 4100-6069 and is the answer not in the manual?

Simplex 4100-6069 Specifications

General IconGeneral
BrandSimplex
Model4100-6069
CategoryControl Unit
TypeFire Alarm Control Panel
ManufacturerSimplex
Voltage120/240 VAC
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing

Summary

Features

BACnet Protocol Reference

Communications via BACnet IP and reference to ANSI/ASHRAE Standard 135.

Connections

RS-232 port for fire alarm system and Ethernet LAN connection.

BACpac Ethernet Module Programming

Pre-programmed with digital points linked to BACnet objects, supports 1000 status changes.

Compatible Simplex Fire Alarm Panels

Lists compatible Simplex panel series for the module.

Listings Reference

UL and ULC listings for the module.

Description

System Integration

Module converts computer terminal info to BACnet for building automation systems.

Response to Fire Alarm Activity

Enables other systems to respond to fire alarm system activity.

Systems Responsibilities

Building Automation Systems

Coordination of electrical and mechanical systems in buildings.

Systems Communications

Communication Between Systems

Using BACnet for status exchange between Simplex and other systems.

Communications Example

Fire detection scenario with BACpac module and building automation.

Diagnostic Reference

Module Converter

Uses Fieldserver Technologies BACnet converter; diagnostic programs available online.

Product Selection

Model Information

Details on BACpac Ethernet Modules 4100-6069 and 4010-9915.

BACnet Protocol Implementation Conformance (PIC) Reference

Device Profile

BACnet Smart Sensor, Actuator, and Application Specific Controller profiles.

Interoperability Building Blocks

Supported BIBBs for data sharing and device management.

Standard Object Types Supported

Lists supported BACnet object types like Analog Input, Binary Output, etc.

Unsupported Properties

Lists properties that are not supported, like CreateObject and DeleteObject.

Additional Property Details

Specifies no additional writeable or proprietary properties or range restrictions.

Data Link Layer Options

MS/TP master or slave options with specified baud rates.

Character Sets Supported

Lists supported character sets like ANSI X3.4 and ISO 8859-1.

Specifications

Input Power

Voltage and current requirements for the module.

Data Input

RS-232 Computer Port Protocol connection to fire alarm control panel.

Data Output

Ethernet compatible communications formatted as BACnet IP.

BACnet Default Settings

Default Device Instance, IP Address, and Subnet Mask.

Status LED Indications

Indicates status of Power, TX, RX, RTX, CTS, DTR, DSR, DCE, and RI.

Module Size

Dimensions for 4100-6069 (2" slot) and 4010-9915 (single block) modules.

Module Description

Details connections for RS-232, power, and LAN suppressor.

Operating Temperature and Humidity

Specifies operating temperature range and humidity limits.