Programming,
Continued
How to Download Data
Use the following procedure to download data to the Graphical LCD Annunciator.
1.
2.
On your PC, go to the COMLCD directory.
At the prompt, type comlcd and enter the ‘tjobname” in the field when prompted.
The COMLCD program process is automatic. .When the process is finished,
continue with Step 3.
3.
4.
Place Jumper Pl on the Graphical LCD Annunciator card in Position 2,3.
Connect a 733-794 Download Cable from the PC’s serial port to P4 on the
Graphical LCD Annunciator card.
5.
6.
7.
8.
9.
Press Reset Button SW1 on the Graphical LCD Annunciator card.
On your PC, type download cjobname>.bin <commport-number (either 1 or
2)) <9600 (baud rate)> and press the Enter key.
When the download is complete, move Jumper Pl on the Graphical LCD
Annunciator card back to Position 1,2.
Remove the download cable.
Press Reset Button SW1 on the Graphical LCD Annunciator card.