Use for installed system expansion applications:
Refer to page 7 for appliance compatibility details
For new addressable notification fire alarm control panel
applications, refer to data sheet S4100-0100
TrueAlert Addressable Operation Features
Each individually addressed notification appliance
receives power and control over a single wire pair
providing:
Supervised wiring connections to each appliance that
support using “T-tapped” wiring for Class B circuits
(Class A circuits require in/out wiring)
Horns sounding with selectable high or low output, as
Temporal 3 or March Time pattern (60 or 120 bpm), or
Steady On, controlled separately from visible appliances
on the same two-wire circuit
Visible appliances operating synchronized at 1 Hz
Control over power limited, isolated output Signaling
Line Circuits (SLCs) with up to 63 addressable
appliances per SLC, and up to 189 appliances per control
source (refer to page 7 for detailed SLC ratings)
Control sources selectable to provide individual appliance
magnetic test mode and appliance LED polling indicator
4100ES, 4100U and 4010ES systems also provide
additional control capabilities using Virtual NAC
(VNAC) appliance groupings across SLCs and across
control sources
Class B, “T-tapped” wiring advantages:
Less wiring distance is required since traditional
end-of-line Class B wiring supervision is not needed
With less wiring distance required, voltage drops can be
reduced, allowing more appliances per wire run
UL listed to Standard 864*
4100ES TrueAlert Power Supplies (TPS)
For mounting in 4100ES/4100U control panels:
Three, 3 A, SLCs (Special Application rating)
TrueAlert Addressable Controllers
Remote mounted control panel that provides:
Three, 2.5 A, SLCs (Special Application rating)
An 8 A power supply/battery charger for internal
batteries up to 12.7 Ah or up to 18 Ah in external cabinet
Multiple communications formats are available:
Remote Unit Interface (RUI) communications
from Simplex
®
4100ES/4010ES/4100U/4120/4100/4020
fire alarm control panels (4100U/4120/4100/4020
requires rev. 9 software or higher) assigns an address
point with custom label to each appliance for individual
trouble reporting
IDNet communications from Simplex 4010 fire alarm
control panels provide individual or multiple channel
control using a single IDNet address
Wired control from conventional NACs connects with
multiple options
ALARMFIRE
PULL DOWN
Optional IDNet Channel Repeater
SIMPLEX TIME RECORDER CO.
4090-9101
MONITOR ZAM, CLASS B
INSTAL. IN STR. 574-183
DATE CODE:
1
5
6
7
8
1
2
3
4
1
2
3
4
5
6
7
8
+ 24V
0V
+IDNET
- IDNET
ZONE PWR +
ZONE PWR -
IDC +
IDC -
Three TrueAlert
SLC Channels
4010 Fire Alarm
Control Panel
4100ES, 4100U, 4010ES,
4100, 4120, or 4020 Fire
Alarm Control Panel
or Fiber Optic IDNet
Communications
RUI Communications
or IDNet
Communications
FIRE ALARM
CO NTRO L
DISCO NNECT
POW ER BEFO
SERVICING
CAUTI O N
** SYSTEM I S NO RMAL * *
12:02:15pm Mon 9-Feb-98
SUPV
ACK
SYSTEM
SUPERVISO RY
ALARM
ACK
FIRE
ALARM
TROUBLE
ACK
SYSTEM
TROUBLE
ALARM
SILENCE
ALARM
SILENCED
SYSTEM
RESET
AC
PO W ER
TrueAlert
Addressable
Controller
input options
IDNet Fiber
Optic Transmitter
or Wired Control
**SYSTEM IS NORMAL**
12:02:15pm Fri 19-Feb-99
ALARM
ACK
SUPV
ACK
TROU B LE
ACK
ALARM
SILE N C E
SYSTEM
RESET
FIRE
ALARM
SYSTEM
SUPERVISORY
SYSTEM
TROUBLE
ALARM
SILE N C ED
AC
POW ER
Non-Addressable
Fire Alarm
Control Panel
SIMPLEX TIME RECORDER CO.
4090-9101
MONITOR ZAM, CLASS B
INSTAL. INSTR. 574-183
DATE CODE:
1
5
6
7
8
1
2
3
4
1
2
3
4
5
6
7
8
+ 24V
0V
+IDNET
- IDNET
ZONE PWR +
ZONE PWR -
IDC +
IDC -
TrueAlert addressable
notification appliances
TrueAlert
Isolator Module
PO W E R
BEFORE
SERVI CING
CAUTION
DISCONNECT
TrueAlert Addressable Controller
TM
or
or
4100ES Fire Alarm
Control Panel with TPS
TrueAlert Addressable Operation Reference Diagram
TrueAlert Addressable Controllers (Contd.)
Extensive internal diagnostics include:
LED status indicators that identify channel and trouble
Support for host fire alarm control panel WALKTEST
system test with IDNet or RUI communications**
Status monitoring of battery, input power, and earth
faults
Optional internal modules:
Class A Three Channel Adapter Module
IDNet Communications: Repeater or Fiber Optic
Receiver/Repeater; models for Class A or Class B
External accessories:
IDNet communication fiber optic transmitters
Remote TrueAlert communications isolator 4905-9929,
refer to data sheet S4905-0001 for details
External battery cabinet for 18 Ah batteries
* NOTE: Model 4009-9501 (240 VAC input) is not included in these listings. Refer to
page 2 for specific applicable listings by model. 4009-9401 (120 VAC input) has been
approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the
California Health and Safety Code. See CSFM Listing 7310-0026:214 for allowable values
and/or conditions concerning material presented in this document. 4009-9401 is accepted
for use – City of New York Department of Buildings – MEA35-93E. Additional listings may
be applicable; contact your local Simplex product supplier for the latest status. Listings
and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection
Products..
TrueAlert Addressable Notification Reference
UL, ULC, CSFM Listed; FM Approved; TrueAlert Addressable Operation Reference &
MEA (NYC) Acceptance* 4009 Series TrueAlert Addressable Controller
S4009-0003-10 9/2015