Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4905-0006-5 4/2013
www.simplexgrinnell.com
© 2013 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA is a trademark of the National Fire
Protection Association.
4" square cover plate, RACO 752
or equal (supplied separately)
Mounting Box (supplied separately), 4" square
(102 mm), minimum depth = 2-1/8" (54 mm),
RACO 232 or equal
POW ER
BEFORE
SERVICING
CAUTIO N
DISCO NNECT
4009 IDNet NAC EXTENDER
TM
Dedicated control NAC to the next Temporal
Code 4 Module, up to 20 total maximum; requires
end-of-line resistor per source NAC requirements
Fire Alarm Control Panel
(4100ES shown for reference)
4009 IDNet NAC Extender (shown, uses IDNet
communications) or Remote 4100ES MINIPLEX
transponder with NACs (uses RUI communications)
Dedicated control NAC
4098-9798 CO
Sensor Sounder
Base*
NAC input to TC4
Module, 3 A maximum
IDNet or RUI Communications
per system requirements
ON
1 2
ON
1 2
4905-9835 Temporal Code 4 (TC4) Module
TC4 NAC output, 3 A maximum
4901-9820 Horn, 4903 Series 4-wire A/V horn,
or other compatible (not SmartSync control)
24 VDC audible notification appliances
Appliance NACs require
end-of-line resistor per
source NAC requirements
* Note: IDNet communications wiring
(not shown) is required to connect
to each 4098-9798 CO Sensor
Sounder Base
Document Description Document Description
579-840 Installation Instructions S4010-0004 4010ES Control Panel
S4098-0041 CO Sensor Base data sheet S4901-0010 4901-9820 Horns
S4100-0031 4100ES Basic Reference S4903-0011 4903 Series 4-wire A/Vs
Mounting Reference
System Connection Reference
Additional Reference