SINAMICS G120
Standard inverters 0.37 kW to 250 kW (0.5 hp to 400 hp)
PM240 Power Modules –
0.37 kW to 250 kW (0.5 hp to 400 hp)
4/38
Siemens D 11.1 · 2009
4
■
Technical specifications
Line supply voltage
380…480V 3AC
PM240 Power Modules
Without integrated line filter 6SL3224-
0BE22-2UA0
6SL3224-
0BE23-0UA0
6SL3224-
0BE24-0UA0
6SL3224-
0BE25-5UA0
6SL3224-
0BE27-5UA0
With integrated line filter 6SL3224-
0BE22-2AA0
6SL3224-
0BE23-0AA0
6SL3224-
0BE24-0AA0
6SL3224-
0BE25-5AA0
6SL3224-
0BE27-5AA0
Output current
at 50 Hz 400 V 3 AC
• Rated current I
rated
1)
A 5.9 7.7 10.2 18 25
• Base load current I
L
1)
A 5.9 7.7 10.2 18 25
• Base load current I
H
2)
A 5.9 7.7 10.2 13.2 19
• I
max
A 11.8 15.4 20.4 26.4 38
Rated power
• based on I
L
kW (hp) 2.2 (3.0) 3 (4) 4 (5) 7.5 (10) 11 (15)
• based on I
H
kW (hp) 2.2 (3.0) 3 (4) 4 (5) 5.5 (7.5) 7.5 (10)
Rated pulse frequency
kHz 4 4 4 4 4
Efficiency
η
0.95 0.95 0.95 0.95 0.95
Power loss
(at rated current)
kW 0.14 0.16 0.18 0.24 0.30
Cooling air requirement m
3
/s 0.024 0.024 0.024 0.055 0.055
Sound pressure level L
pA
(1 m)
dB <50 <50 <50 <60 <60
24 V DC power supply
for Control Unit
A 1 1 1 1 1
Rated input current
3)
• with line reactor A 6.1 8 10.4 18.7 26
• without line reactor A 7.6 10.2 13.4 21.9 31.5
Max. length of cable to
braking resistor
m 15 15 15 15 15
Line supply connection
U1/L1, V1/L2, W1/L3
Screw terminals Screw terminals Screw terminals Screw terminals Screw terminals
• Conductor cross-section mm
2
1…6 1…6 1…6 2.5 … 10 2.5 … 10
Motor connection
U2, V2, W2
Screw terminals Screw terminals Screw terminals Screw terminals Screw terminals
• Conductor cross-section mm
2
1…6 1…6 1…6 2.5 … 10 2.5 … 10
DC link connection,
connection for the braking
resistor
DCP/R1, DCN, R2
Screw terminals Screw terminals Screw terminals Screw terminals Screw terminals
• Conductor cross-section mm
2
1…6 1…6 1…6 2.5 … 10 2.5 … 10
PE connection
On housing with
M5 screw
On housing with
M5 screw
On housing with
M5 screw
On housing with
M5 screw
On housing with
M5 screw
Motor cable length
4)
, max.
• Shielded m 50 50 50 50 50
• Unshielded
m 100 100 100 100 100
Degree of protection
IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm 153 153 153 189 189
•Height mm 270 270 270 334 334
•Depth
- without Control Unit mm 165 165 165 185 185
- with Control Unit mm 230 230 230 250 250
Frame size FSB FSB FSB FSC FSC
Weight, approx. kg 4 4 4 7 7
1)
The rated output current I
rated
and the base load current I
L
are based on
the duty cycle for light overload (LO).
2)
The base load current I
H
is based on the duty cycle for high overload (HO).
3)
The input current depends on the motor load and line impedance. The
input currents apply for a load at rated power (based on I
rated
) for a line
impedance corresponding to u
K
= 1 %. These current values without line
reactor are stamped on the rating plate of the Power Module.
4)
Max. motor cable length 25 m (shielded) for PM240 Power Modules with
integrated line filter to maintain the limit values of EN 61800-3 Category C2.