DC INVERTER U-MATCH AIR CONDITION                                       MAINTENANCE 
 
97
MAINTENANCE 
1 TROUBLE TABLE   
Table 1 Fault Display on Indoor Wired controller: 
Trouble 
Code 
Trouble 
Name 
Origin of   
Trouble Signal
Control Description 
E0 
Water Pump 
Malfunction 
Water pump 
If the water-full protection cannot be recovered after 2 hours, it is 
believed that the water pump is failed, in which case all the loads 
will be switched off and cannot be recovered automatically.   
E1 
High Pressure 
Protection of 
Compressor
High-pressure 
Switch 
When high pressure protection is detected for 3 seconds 
successively, all the loads (except the heating 4-way valve) will be 
switched off, in which case all the keys and remote control signals 
except ON/OFF function will be disabled and cannot be recovered 
automatically. To eliminate the fault, it is needed to switch off and on 
the machine or recover from power failure.   
E2 
Indoor 
Anti-frozen 
Protetion 
Indoor evaporator 
sensor 
If detecting that the evaporator sensor is lower than -2  after the ℃
unit has been running for a period of time under cooling or dry 
mode, the unit will report this fault, in which case the compressor 
and outdoor fan will be stopped. The unit will not run until this 
temperature is ≥10  and the compressor is stopped for 3 minutes. ℃
E3 
Low Pressure 
Protection of 
Compressor
Low-pressure 
Switch 
If it is detected within 30 seconds successively that the low-pressure 
switch is cut off under ON or standby state (If the compressor is 
started, the detection will start 3 minutes after the compressor has 
run), the unit will report this fault. For the first two faults within 30 
minutes, the unit can be recovered automatically. If over three times, 
the unit cannot be recovered automatically.   
E4 
Air Discharge 
High-temperatur
e Protection of 
Compressor
Exhaust 
Overtemperature 
Protection 
After the compressor is started, if it is detected within 30 seconds 
successively that the exhaust temperature is 130  or higher, E4 will ℃
be displayed, in which case all the loads (except the 4-way valve o
 
heating) will be stopped. The complete unit can only be recovered 
until the compressor has stopped for 3 minutes and the exhaust 
temperature is lower than 90 . For th℃ is protection occurs three 
times, the complete unit cannot be recovered automatically.   
E5 
Overload 
Proection of 
Compressor
Compressor 
After the unit is energized, if it is detected within 3 seconds 
successively that the compressor overload switch is cut off, it will be 
deemed compressor overload protection. In this case, all the loads 
will be stopped (except the 4-way valve of heating) and E5 will be 
displayed. If the fault is eliminated, the compressor will be restarted 
after 3 minutes. If three compressor overload protections are