DC INVERTER U-MATCH AIR CONDITION                                       MAINTENANCE 
 
108
Malfunction display: E4 Compressor Exhaust High Temperature Protection◆  
Abnormal discharge
temperature
Measure if compressor’s discharge 
temperature has reached 130
N
Y
Y
System pipeline leaks so complementation is 
needed. Please add refrigerant according to the 
amount specified on the nameplate
Measure if temperature sensor’s 
resistance value is correct
Replace relevant 
discharge temperature 
sensor
N
Y
Replace the main board 
of the outdoor unit.
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
PH means that D/C input voltage is too high.
The solution:
1.Pls check the voltage between AC-L and N.If the voltage is 185V~264,that's ok.
2.If the voltage is 185V~264,pls change the main-board of out -door unit.
3.If the ERROR still,Pls change the compressor.