DC INVERTER U-MATCH AIR CONDITION                                       MAINTENANCE 
 
115
2.2 Typical Troubleshooting for A series Outdoor Unit Drive (Inverter) by Single-phase Motor 
(Applicable to
 ASGE-18AI, ASGE-24I, ASGE-36AI) 
PFC module protection◆  
 
E5 displayed on
wired controlle
r
(overcurrent 
protection)
 
Monitor display 
Mainboard indicator
PFC abnorma 
Dark Bright Bright
Dark Blink Bright
Cut off the power for 1 minute 
or reduce the busbar voltage 
to 36V or lower. Then, switch 
on the power again and start 
the machine to run a period o
f 
time. After that, check if the 
fault disappears.   
If the connection cable 
has problem?   
Reconnect or 
replace the cable
If the DC voltage is
stabilized a
t
380±10V after the
voltage has risen.   
PFC board 
damaged. Replace 
with a new PFC 
board 
If the power voltage 
is too low?   
Check if the PFC 
module screws are 
well tightened?   
Normal overcurrent 
protection 
Overheat protection. 
Tighten the screws.   
Caused by interference. 
Check if the high-current 
cables are separated from 
low-current cables.   
Record and feed back
Yes 
Yes 
Yes 
Yes
Yes 
No
No
No
No No