DC INVERTER U-MATCH AIR CONDITION MAINTENANCE
120
Radiator overheat protection
Monitor display
Mainboard indicator
Radiator overheat
protection
Blink Blink Blink
Bright Blink
Bright
If the outdoo
r
unit is in good
radiation?
If the air outlet and return
air inlet of the outdoor uni
t
is short circuited, it will
cause the radiating effect to
become poor.
If the radiato
r
is dirty o
r
blocked?
If the radiator is dirty o
r
blocked, it will cause the
radiating effect to become
poor.
If IPM module is
well tightened?
If IPM module is no
t
tightened, it will cause the
module temperature to
become too high, or even
burn the module.
If the silicate gel
on IPM module is
uniformly coated?
If the coating of silicate gel is not
uniform, it will cause poor radiation to
the module, or uneven distribution o
f
the temperature, or even burn the
module as the sensor cannot detec
t
the temperature in some area is too
high.
If the silicate gel
coated on IPM
module can meet
the requirements?
If the coating of silicate
gel is too thick, it will also
affect the radiating effect
or even burn the module.
Please check if the
sensor is failed, o
r
reinstall the module and
ti
g
hten it.
Record and feed back