DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
2.4 Defrosting
The conditions for starting the defrosting are as follows:
The defrosting is started when one of the following three conditions is satisfied:
The total time for outdoor defrost sensor to run below 3 is longer than 40 minutes and this ℃
temperature is kept lower than -6 for over 3 minutes.℃
The outdoor temperature sensor keeps lower than 3 for at least 80 minutes and keeps lower than
-4 for at least 3 minutes.
The outdoor temperature sensor keeps lower than 3 for at least 120 minutes and keeps lowers
than -3 for at least 3 minutes
The conditions for ending the defrosting are as follows:
The defrosting is ended when one of the following three conditions is satisfied:
When the temperature of o① utdoor heat exchanger rises to higher than 10 .℃
When the temperature of outdoor heat exchanger rises to higher than 8 and this lasts for over 80 ② ℃
Variable Frequency
Compressor
Outdoor fan
Indoor fan
4-way valve
Heating / Defrosting Time Sequence Chart
Defrosting marking
Defrosting frequenc