DC INVERTER U-MATCH AIR CONDITIONERS                                    INSTALLATION 
 
  Minimize the number of elbows on connection pipe.   
  If the connection pipe is longer than 20m, it is needed to check if the lubricating oil in the system is 
enough. Add if needed.   
  The refrigerant charge volume inside the machine is suitable for 7m connection pipe. To extend the 
length of connection pipe, it is needed to add an appropriate quantity of refrigerant. For extension of 
pipe length by every 1 meter, the refrigerant to be added is as follows. The maximum allowable 
length of pipe is as follows.   
  If the height difference between indoor and outdoor units is over 10m, it is required to install an oil 
trap every 6 meters.   
  When the indoor and outdoor units are on different height, please refer to Fig. 30201 for pipe layout.   
       Liquid pipe (i.e. fine pipe) 
- - - - - -Gas pipe (i.e. coarse pipe) 
 
Figure 3-2-1 
Gas pipe 
Outdoor unit
Oil elbow in 
gas pipe
 
One oil trap shall 
be arranged every 
4-6
 m
Liquid pipe 
Indoor unit