DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
4.3 Specification of Power Supply Wire and Air Switch
Model
Power
Supply
Capability of
Air Switch(A)
(Outdoor
/Indoor)
Minimum
Sectional Area of
Earth Wire(mm
2
)
(Outdoor /Indoor)
Minimum
Sectional Area of
Power Supply
Wire(mm
2
)
(Outdoor /Indoor)
ASGE-18I/ ASD-18AI 20/6 2.5/1.0 2.5/1.0
ASGE-24AI/ ASD-24AI 20/10 2.5/1.5 2.5/1.5
ASGE-24AI S/ ASD-24AI S 20/10 2.5/1.5 2.5/1.5
ASGE-36AI/ ASD-36AI 32/10 6.0/1.5 6.0/1.5
ASGE-36AI S/ ASD-36AI S
32/10 6.0/1.5 6.0/1.5
ASGE-42AI-3 S/ ASD-42AI S
32/10 6.0/1.5 6.0/1.5
220-240V~
1 Ph
50HZ
ASGE-36AI-3/ ASD-36AI
25/10 4.0/1.5 4.0/1.5
ASGE-36AI-3 S/ ASD-36AI S
25/10 4.0/1.5 4.0/1.5
ASGE-42AI-3/ ASD-42AI
25/10 4.0/1.
5 4.0/1.5
380-415V~
3 Ph
50HZ
ASGE-18AI/ ASF-18AI
20/6 2.5/1.0 2.5/1.0
ASGE-24AI/ ASF-24AI
20/10 2.5/1.5 2.5/1.5
ASGE-24AI S/ ASF-24AI S
20/10 2.5/1.5 2.5/1.5
ASGE-36AI/ ASF-36AI
32/10 6.0/1.5 6.0/1.5
ASGE-36AI S/ ASF-36AI S
32/10 6.0/1.
5 6.0/1.5
ASGE-42AI-3 S/ ASF-42AI S
32/10 6.0/1.5 6.0/1.5
220-240V~
1 Ph
50HZ
ASGE-36AI-3/ ASF-36AI
25/10 4.0/1.5 4.0/1.5
ASGE-36AI-3 S/ ASF-36AI S
25/10 4.0/1.5 4.0/1.5
ASGE-42AI-3/ ASF-42AI
25/10 4.0/1. 5 4.0/1.5
380-415V~
3 Ph
50HZ