EasyManua.ls Logo

Sinclair SDV4 series - Page 72

Sinclair SDV4 series
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82 Troubleshooting
4.8
P1 malfunction: High pressure protection
High pressure protection
Judge 1: whether the wiring is correct.
Judge 2: whether the wire body is broken.
YES
NO
Connect again.
Judge: short-circuit high pressure switch. Check the
system can operate normally.
NO
Replace the high pressure
switch.
YES
Check whether the cooling system operates normally.
Replace the main PCB.
NO
Judge 3: whether high pressure of the system is too high.
YES
Stop the system.
NO
Judge 4: whether side air duct of outdoor unit meets the
standard.
NO
Rectify the air duct
YES
Judge 5: whether the heat exchanger needs cleaning.
YES
Clean
NO
Judge 7: whether the pipeline is blocked.
YES
Rectify the pipeline.
Judge 6: whether the throttle part is stuck, stocked or works
abnormally.
YES
Change throttle parts to
clean the blockages.
LED displays P1

Other manuals for Sinclair SDV4 series

Related product manuals