SJE Rhombus Installer Friendly Series User Manual

SJE Rhombus Installer Friendly Series
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
22650 County Highway 6
P.O. Box 1708
Detroit Lakes, Minnesota 56502 USA
1-888-DIAL-SJE (1-888-342-5753)
Phone: 218-847-1317
Fax: 218-847-4617
E--mail: customer.service@sjerhombus.com
Website: www.sjerhombus.com
©SJE-Rhombus
Printed in USA
1036677 • Rev B 12/14
Manufactured by:
Warranty void if panel is modi ed.
Call factory with servicing questions:
1-800-RHOMBUS
(1-800-746-6287)
This control panel must be installed and serviced by a
licensed electrician in accordance with the National Electric Code
NFPA-70, state and local electrical codes. All conduit running from
the sump or tank to the control panel must be sealed with conduit
sealant to prevent moisture or gases from entering the panel. NEMA
4X enclosures are for indoor or outdoor use, primarily to provide
a degree of protection against corrosion, windblown dust and rain,
splashing water and hose-directed water. Cable connectors must
be liquid-tight in NEMA 4X enclosures.
The C-Level sensor is suitable for use in sewage applications.
Do NOT use in potable water.
Installer Friendly Series
®
(IFS) control panels are designed to control
pump(s). The controller records number of pump cycles, elapsed run
time, alarm counts, and signal error counts.
Mounting the Control Panel
Note: The control panel should not be mounted in a location that may
be subject to submersion.
1. Determine mounting location for panel. If distance exceeds the
length of either the sensor or oat cables or the pump power
cables, splicing will be required. Note: For splicing C-Level cord,
use only shielded cable. Splice conductors as well as shielding.
Maximum total cable length is 300 feet. For outdoor or wet instal-
lation, we recommend the use of an SJE-Rhombus
®
liquid-tight
junction box with liquid-tight connectors to make required connec-
tions. You must use conduit sealant to prevent moisture or
gases from entering the panel.
2. Mount control panel with mounting devices furnished.
3. Determine conduit entrance locations on control panel. Check
local codes and schematic for the number of power circuits re-
quired. (Sensor cable requires separate conduit from power
and pump cables.)
Note: Be sure the proper power supply voltage, amperage, and phase
meet the requirements of the pump motor(s) being installed. If in
doubt, see the pump identi cation plate for voltage/phase require-
ments.
4. Drill proper size holes for type of connectors being used.
Note: If using conduit, be sure that it is of adequate size to pull the
pump cable(s) through.
5. Attach cable connectors and/or conduit connectors to control
panel.
FOR INSTALLATION REQUIRING A SPLICE, FOLLOW STEPS 6-10;
FOR INSTALLATION WITHOUT A SPLICE, GO TO STEP 11.
Installer Friendly Series
®
SJE-Rhombus
®
Type IFS w/C-Level
Sensor
Installation Instructions and Operation/Troubleshooting Manual
Installation

Other manuals for SJE Rhombus Installer Friendly Series

Question and Answer IconNeed help?

Do you have a question about the SJE Rhombus Installer Friendly Series and is the answer not in the manual?

SJE Rhombus Installer Friendly Series Specifications

General IconGeneral
BrandSJE Rhombus
ModelInstaller Friendly Series
CategoryControl Panel
LanguageEnglish

Summary

Installation

Mounting the Control Panel

Detailed steps for physically attaching the control panel to a suitable location.

Installation of C-Level Sensor and Floats

Instructions for correctly positioning and securing the C-Level sensor and optional floats.

Operations

Level Indicators

Explanation of illuminated indicators on the control panel during operation.

Green Control and Alarm Power Indicators

Describes the function of power and alarm indicators on the circuit board.

LED Display

Information on the LED display's use for settings and cycle data.

Viewing Panel Settings and Cycle Data

Guide on navigating and viewing panel settings and operational data.

Programming Panel Settings

Steps and parameters for entering program mode and setting panel configurations.

Selecting Time Dose or Demand Dose

Procedure for configuring the panel for timed or demand dose operation in the field.

Troubleshooting

C-Level Sensor Issues

Common problems and checks for the C-Level sensor for accurate readings.

Fuse Check

Procedure for testing the control panel's fuse continuity.

Alarm Light Functionality

How to test the alarm light and when to replace it.

Alarm Horn Functionality

How to test the alarm horn and when to replace it.

Warranty Information