29
Battery low voltage cut-out:
The cut-out threshold is 1.8 V/cell ±5 %.
The element causing the cut-out will be in the + position.
6 Maintenance
In order to ensure maximal and durable service, we strongly recommend that your product be maintained
clean and ensure that it is installed in a dry and ventilated location. We shall in no case be liable for damages
associated with improper use or incorrect maintenance of the equipment.
WARNING
Replacing the original battery with a battery of incorrect type may result in an explosion hazard.
Used batteries must be disposed of in compliance with recycling requirements.
7 Fuse protections
7.1 24 V versions
24 V
2
24 V
3
24 V
4
24 V
6
24 V
8
24 V
12
24 V
16
24 V
24
F1 (mains): rating - type
size - breakin
capacit
3.15 A Time lag
5x20 - 1500
2 A Time lag
5x20 - 1500
6.3 A Time lag
5x20 - 1500
8 A Time lag
5x20 - 1500
F7, F8 (load):
ratin
- t
pe - size
3.15 A Time lag
5x20
6.3 A Time lag
5x20
12.5 A Time lag
5x20
25 A gG
10.3x38
FBat (battery):
ratin
- t
pe - size
Fuse with automatic reset 16 A gG
10.3x38
32 A gG
10.3x38
7.2 48 V versions
48 V
2
48 V
3
48 V
4
48 V
6
48 V
8
48 V
12
F1 (mains): rating - type
size - breakin
capacit
2 A Time lag
5x20 - 1500
6.3 A Time lag
5x20 - 1500
8 A Time lag
5x20 - 1500
F7, F8 (load):
ratin
- t
pe - size
3.15 A Time lag
5x20
6.3 A Time lag
5x20
12.5 A Time lag
5x20
FBat (battery):
ratin
- t
pe - size
Fuse with automatic
reset
12.5 A Time lag
5x20
20 A Time lag
10.3x38