Effective: October 2016
Remote Releasing Module
DESCRIPTION
The Remote Releasing Module (RRM) is a UL Listed, FM Approved
SmartOne
®
Field Device. The RRM provides the ability to remotely activate
extinguishing-system control devices. Connection is via the SmartOne
com-
patible control panel’s Signaling Line Circuit (SLC). The module is eld-pro-
grammable using the control panel keypad or Hand-Held Programmer.
The RRM provides internal supervision of communication with the control
unit, connections to external power supply, and memory status.
Solenoid release circuits are power-limited and supervised for short circuit
by using an In-line Releasing-Circuit Device (P/N 06-220023-001). In the
event of a ground fault, open, short or a relay contact failure, the device
will transmit a trouble status to the control unit.
A status LED is mounted on the RRM and indicates the module’s status:
Normal is indicated by a ash every 9 seconds; Output Activity is indicated
by the LED on continuously (no ashing); Trouble is indicated by the LED
being OFF.
The RRM is intended for indoor dry location use, and is available in two
models, one for mounting in a standard electrical box and a second model
for mounting in suitable UL-864 Listed cabinets.
P/N 70-600000-001: Standard Mounting
North American 4-11/16 in. electrical box with a double gang plaster
ring (Rayco Model 841 or equivalent), 1/2 in. raised
4 in. square, 2-1/8 in. deep electrical box
P/N 70-600000-002: In-Cabinet Mounting
Any suitable UL-864 Listed enclosure with no other electronics.
The module terminal block will accept #12, #14, #16 and #18 AWG wire
(4.0 mm
2
, 2.5 mm
2
, 1.5 mm
2
and
1.0 mm
2
respectively). Size #18 being a
minimum requirement. The use of solid wire is recommended.
TM
KIDDE-FENWAL INC.
400 MAIN STREET, ASHLAND, MA 01721
TEL: (508) 881-2000 FAX: (508) 881-8920
This literature is provided for informational purposes only.
KIDDE-FENWAL,INC. assumes no responsibility for the
product’s suitability for a particular application. The product
must be properly applied to work correctly.
If you need more information on this product, or if you have
a particular problem or question, contact KIDDE-FENWAL
INC., Ashland, MA 01721. Telephone: (508) 881-2000
06-236636-001 Rev. AD ©2016 Kidde-Fenwal, Inc.
INSTALLATION INSTRUCTIONS
This device complies with Part 15 of the FCC rules. Operation is subject to the following two
conditions: (1) This device may not cause any harmful interference, and (2) This device must
accept any interference received, including interference that may cause undesired operation.
Control Unit
Part Number
Installation,
Operation and
Maintenance Manual
Part Number
Configuration
Software
User's Guide
Part Number
FenwalNET 6000:
74-600000-001 06-236529-001 06-236529-002
74-600000-510 06-236529-001 06-236529-002
ARIES:
76-600000-004 06-236530-001 06-236530-002
FenwalNET 8000-ML:
74-800100-001 06-237041-001 06-237042-001
74-800101-002 06-237041-001 06-237042-001
74-800200-001 06-237041-001 06-237042-001
74-800201-002 06-237041-001 06-237042-001
ARIES NETLink:
76-800100-001 06-237058-001 06-237059-001
76-800101-002 06-237058-001 06-237059-001
76-800200-001 06-237058-001 06-237059-001
76-800201-002 06-237058-001 06-237059-001
74-800102-001 06-237041-001 06-237042-001
74-800202-001 06-237041-001
06-237042-001
76-800102-001 06-237058-001 06-237059-001
76-800202-001 06-237058-001 06-237059-001
Question and Answer IconNeed help?

Do you have a question about the SmartOne 70-600000-001 and is the answer not in the manual?

Summary

Remote Releasing Module Description and Models

RRM Overview and Status LED

Explains the RRM's function, supervision, and LED status indications.

Standard Mounting Model Requirements

Specifies electrical box requirements for the standard mounting model.

In-Cabinet Mounting Model Requirements

Specifies enclosure requirements for the in-cabinet mounting model.

Specifications and Ordering Information

Device Specifications

Details on operating voltage, current, temperature, humidity, and construction.

Electrical Box Compatibility

Lists compatible electrical boxes for RRM installation.

Ordering Information

Lists part numbers for the RRM and related components.

Installation and Wiring

In-Cabinet Mounting Procedure

Step-by-step guide for mounting the RRM in a UL-864 listed enclosure.

RRM Wiring Diagram

Illustrates connections for the Remote Releasing Module.

General Wiring Notes

Important considerations for wiring the RRM, including wire gauge and isolation.

Installation Details and Supervision

Electrical Box Installation

Instructions for installing the RRM in 4-11/16 in. or 4 in. square electrical boxes.

Circuit Supervision

Explains how circuits are supervised for faults and power limitations.

Overview

The Remote Releasing Module (RRM) is a UL Listed, FM Approved SmartOne® Field Device designed to remotely activate extinguishing-system control devices. It connects via the SmartOne compatible control panel's Signaling Line Circuit (SLC) and is field-programmable using the control panel keypad or a Hand-Held Programmer.

Function Description:

The RRM provides the capability to initiate extinguishing system actions. It includes internal supervision of communication with the control unit, connections to an external power supply, and memory status. Solenoid release circuits are power-limited and supervised for short circuits using an In-line Releasing-Circuit Device (P/N 06-220023-001). In the event of a ground fault, open circuit, short circuit, or relay contact failure, the device transmits a trouble status to the control unit.

Important Technical Specifications:

  • Operating Voltage: 24 VDC Nominal
  • Device Current (Remote Supply): 6.1 mA Standby, 45 mA Alarm (Excluding Releasing Devices)
  • Device Current (SLC): 410 μA Standby and Alarm
  • Operating Temperature Range: 32°F to 120°F (0°C to 49°C)
  • Operating Humidity Range: 0% to 93% RH
  • Construction: High Impact Polymer Faceplate with a 16 gauge Aluminum Bracket
  • Shipping Weight: 10.5 oz (298 g)
  • Releasing Circuit Output Current: 2.4A Max. @ 24.0 VDC
  • Trouble Circuit Input: 4.7K End of Line Resistor, "Open" contact = normal condition
  • SLC Wiring Configuration: Class A, Class B, Class A, Style-7
  • Wiring: Unshielded (See Note 12 for use of shielded wire)
  • Terminal Connection: Supports wiring from #18 AWG (1.0 mm²) to #12 AWG (4.0 mm²). Solid wire is recommended.
  • Module Volume: 8.94 cubic-inches.

Usage Features:

  • Programming: The module address can be programmed prior to installation using a handheld programmer (requires a 24 VDC power supply) or via the control panel/configuration software. All other configurations are set using the control panel or configuration software.
  • Mounting Options:
    • Standard Mounting (P/N 70-600000-001): Designed for North American 4-11/16 in. electrical boxes with a double gang plaster ring (Rayco Model 841 or equivalent, 1/2 in. raised) or 4 in. square, 2-1/8 in. deep electrical boxes.
    • In-Cabinet Mounting (P/N 70-600000-002): Intended for mounting inside any suitable UL-864 Listed enclosure with no other electronics. Requires a minimum 1/2 in. clearance between the RRM(s) and the enclosure.
  • LED Status Indicator:
    • Normal: Flash every 9 seconds.
    • Output Activity: LED on continuously (no flashing).
    • Trouble: LED OFF.
  • Releasing Device Compatibility:
    • Single-Loop Panel Activation: Up to 4 groups of 16 RRMs activated simultaneously.
    • Multi-Loop Panel Activation: Up to 7 groups of 20 RRMs activated simultaneously.
    • Refer to the applicable Installation, Operation and Maintenance manual and Configuration Software User's Guide for specific information on RRM activation and compatible releasing devices.
  • Wiring Guidelines:
    • Strip 1/4 in. from the ends of all wires connecting to the terminal block.
    • Ensure all wiring is free of opens, shorts, and ground faults.
    • Verify all wires are insulated up to and touching the terminal block, and that each terminal screw is tight.
    • Connect Earth-Ground to the green screw on the mounting bracket.
    • Do not attach power-limited and non-power-limited wiring to the same terminal block.
    • Route non-power-limited wires at least 1/4 in. away from all power-limited wiring.
    • The use of shielded wire is not allowed for the Release Circuit, PSU Trouble Circuit, and 24VDC Power Circuit, except for very short runs (combined total of 50 feet maximum). Total combined shielded wire on all these circuits (excluding SLC) must not exceed 200 feet.
    • For Power-Limited Circuits, use Type FPL, FPLR, or FPLP cable per Article 760 of the National Electrical Code (NEC).
    • An extension ring or deeper box can be used for ease of wiring, especially with solid wire.

Maintenance Features:

  • Supervision: Each circuit is supervised for short circuit (only when using inline device 06-220023-001 for solenoids), open circuit, and ground faults to be listed as power limited. Initiators are an exception, not supervised for short circuits, and not listed as Non-Power Limited.
  • Troubleshooting: In the event of a ground fault, open, short, or relay contact failure, the device transmits a trouble status to the control unit.
  • Safety Precaution: Ensure all releasing devices are physically disconnected from the releasing circuits before performing any testing or maintenance.
  • Field Serviceability: The RRM is shipped as an assembled component and is not field-serviceable.