3
SPECIFICATIONS
- IMPORTANT -
THE SPECIFICATIONS GIVEN IN THIS PUBLICATION DO NOT INCLUDE NORMAL MANUFACTURING TOLERANCES.
THEREFORE, THIS UNIT MAY NOT MATCH THE LISTED SPECIFICATIONS EXACTLY. ALSO, THIS PRODUCT IS TESTED
AND CALIBRATED UNDER CLOSELY CONTROLLED CONDITIONS AND SOME MINOR DIFFERENCES IN PERFORMANCE
CAN BE EXPECTED IF THOSE CONDITIONS ARE CHANGED.
MODEL
F72A-1003
F72A-1011
F72B-1003
F72B-1011
NO. OF CELLS
1
1
2
2
RATED VOLTAGE
100-120 Vac
200-240 Vac
100-120 Vac
200-240 Vac
FREQUENCY
50-60 Hz
50-60 Hz
50-60 Hz
50-60 Hz
POWER, NOMINAL
40 Watts
40 Watts
50 Watts
50 Watts
POWER, MAXIMUM
90 Watts
90 Watts
100 Watts
100 Watts
WEIGHT, SHIPPING
200 Lb.
200 Lbs.
300 Lbs.
300 Lbs.
WEIGHT, INSTALLATION
150 Lbs.
150 Lbs.
250 Lbs.
250 Lbs.
AMBIENT TEMPERATURE RATING: Air flow through cells -- 125°F maximum, 40°F minimum
Electronic cells -- 250°F maximum during washing or drying
CABINET: 16 gauge galvanized steel, hinged filter access door
POWER SUPPLY: Solid state, dual voltage power supply provides 9400 Vdc to the ionizer wires and
4700 Vdc to the collector positive plates. The solid state power supply is self-regulating so the output
voltage remains constant over a wide range of cell dirt loading conditions.
ELECTRONIC CELL SPECIFICATIONS, PN 38010:
Dimensions: 24.25” x 24.125” x 10.75” deep
Cell Weight: 60 Lbs.
Collection Area: 240 sq. ft.
Voltage Gradient: 20,000 volts per inch
Ionizer Wires: 11 wires per cell, .010” diameter, tungsten
MOUNTING: a) Vertical, standing or hanging cabinet with horizontal air flow
b) Horizontal mounting with vertical air flow
DIMENSIONS: See Fig. 1, Pg. 4
RECOMMENDED AIR FLOW (CFM) WITH CORRESPONDING PRESSURE DROP AND EFFICIENCY RATING
TABLE 1
F72A
F72B
EFFICIENCY
a
(PERCENT)
WATER
PRESSURE DROP
cfm
m³/hr.
cfm
m³/hr.
cfm
m³/hr.
in.
kPa
1,000
1,500
2,000
2,500
3,000
1,699
2,548
3,398
4,248
5,096
2,000
3,000
4,000
5,000
6,000
3,398
5,097
6,796
8,495
10,194
4,000
6,000
8,000
10,000
12,000
6,796
10,194
13,592
16,990
20,388
99
99
95
90
80
0.06
0.12
0.22
0.33
0.49
.015
.030
.055
.083
.122
*Efficiency ratings based on National Bureau of Standards Dust Spot Method and American Society of Heating, Refrigerating and