6.3.5 Start button
In pulse mode, the Start button is used to activate the signals for
opening and closing.
Command sequence: Open – Stop – Close – Stop etc.
The first command after switching on the control unit (Power ON) is
“Open”.
6.4 Connecting the warning light and the lighting
1. Internal lighting
2. External warning light
The external warning light is powered over the control unit (230V AC,
max. 40 W). It has two flashing patterns:
• slow (every 2 seconds) while the door is moving and during the
early warning function;
• fast (every half-second) while the door is moving in dead man
mode.
The warning light during door movement can be set over DIP switch 1:
• to “OFF”: warning light flashes;
• to “ON”: warning light shines steadily.
The internal lighting (230 V AC, max. 15 W) behaves in the same way
as the external warning light and has the same flashing pattern.