Permissibleratedcross-sectionforconnectingcables
• at terminals 1 to 12: 1.5 mm² – 4.0 mm²
• atterminals13to36:0.2mm²–1.5mm²
2
N
~ 230 V
~ 230 V
M
PE
PE
L1
N
1. Mains connection 230 V AC ± 10%
2. Motor connection (max. motor output 1000 W)
26 28 30 32 34 36
25 27 29 31 33 35
14 16 18 20 22 24
13 15 17 19 21 23
3. Install jumper (included in scope of delivery) if the following elements are not
connected:
• Photocell:betweenterminals29and31
• Anti-dropdevice:betweenterminals20and22
• EmergencySTOPswitch:betweenterminals22and24
• 3-waybutton:betweenterminals17and19(Stopbutton)