Features
1If the fault of the product or abnormal system lead to a serious accident, please set the appropriate circuit protection outside.
2Before the connection completely, please do not power. Otherwise it may result in electric shock, fire, malfunction.
3Do not use the product out of scope of specifications range. Otherwise, it may result in fire, malfunction.
4Do not use in places with flammable and explosive gas.
5 Do not touch the site of high voltage power terminal site after power. Otherwise, there is danger of electric shock.
6Do not disassemble, repair and modify this product. Otherwise,it may result in electric shock, fire, malfunction.
Safety Caution
SF Series
KKSFE03-A/2-20220927Page01
1.Installation
1This product is used in the following environmental standards.
IEC61010-1[Overvoltage categoryⅡ、class of pollution 2]
2This product is used in the following scope:surrounding environment, temperature, humidity and environmental conditions.
Temperature050℃;Humidity4585%RH;Environment conditionIndoor warranty,The altitude is less than 2000m.
3Please avoid using in the following places:
The place will be dew for changing temperature;with corrosive gases and flammable gas;with vibration and impact;with water, oil, chemicals,
smoke and steam facilities with Dust, salt, metal powder;and with clutter interference, static electric and magnetic fields, noise;where has air
conditioning or heating of air blowing directly to the site.
4On the occasion of the installation, please consider the following before installing several.
In order to protect heat saturated, please ensure adequate ventilation space.
Please consider connections and environment,and ensure that the products below for more than 50mm space.
Please avoid to installed over the machine of the calorific value(Such as heaters, transformer, semiconductor operations, the bulk resistance).
When the surrounding is more than 50, please using the force fan or cooling fans.But don't let cold air blowing directly to the product.
In order to improve the anti - interference performance and security, please try to stay away from high pressure machines, power machines to
install.Don`t install on the same plate with high pressure machine and the product.
The distance should be more than 200mm between the product and power line.
Warning
● The upper line red LED display real time,maximum & minimum value,and the lower line greenLED display measure unit or alarm value.
● Support 3 alarms output maximum
● Support many kinds of linear signal inputs or temperature sensor signals
● Optional 4-20mA DC transmition output , can modify the transmition range and make calibration.
●RS485 communication and Modbus-RTU protocol
●Power supply 100 240V AC/DC
●Isolated DC24V voltage output30mA
● Peak value hold function, easy to record the maximum and minimum measurement data
●easy to operate, economical and practical.
SF Sensor Meter User Manual
The instruction explain instrument settings,connections,name and etc,please read carefully before you use the temperature controller.
Caution
1This product should not be used in a nuclear plant and medical equipment which associated with human life.
2Some time,it will happen radio interference when the product uses in home environment.It should take adequate countermeasures.
3This product has electric shock protection through improved insulation.And when using the product and connecting,it subject to
compliance with specifications.
4In order to avoid lighting surge,it should set appropriate surge suppression circuits when the product uses in the environment where
the total cable lengh more than 30 metre.
5The product uses in disk,and avoid to touch the part of high voltage,please take the necessary measure on the final product.
6Please observe the precautions in this manual, otherwise there is risk of causing significant harm or accident.
7Please abserve the regulation when wiring.
8To prevent to damage the machine and prevent to machine failure, the product is connected with power lines or large capacity input and output
lines and other methods please install proper capacity fuse or other methods of protection circuit.
9Please don't put metal and wire clastic mixed with this product,otherwise it may lead to electric shock, fire, fault.
10Please tighten screw torque according to the rules.If not,it may lead to electric shock and fire.
11In order not to interfere with this products to dissipate heat, please don't plug casing around the cooling vent hole and equipment.
12Please don`t knock or rub the panel with rigid thing.
13The readers of this manual should have basic knowledge of electrical,control, computer and communications.
14The illustration, example of data and screen in this manual is convenient to understand,instead of guaranteeing the result of the operation.
15In order to use this product with safety for long-term,regular maintenance is necessary. The life of some parts of the equipments are by
some restrictions, but the performance of some will change for using many years.
16Without prior notice, the contents of this manual will be change. We hope these is no any loopholes, if you have questions or objections, please
contact us.
Caution of Install & Connection
.Specification
.Order Model Information
.Model Illustration
SF□-A0
SF□-R20B
SF□-IR20B
SF□-IR28B
SF□-A0-T
SF□-R20B-T
SF□-R28B-T
SF□-IR20B-T
SF□-IR28B-T
SF series sensor Indicator
CVersion
B: With DC 24V auxiliary voltage Blank:No auxiliary voltage
T: Temperature sensor input Blank:Voltage,current input
0: without RS485 8:with RS485 communication
I: With DC 4-20mA transmition output Blank: No transmition output
4: 48W*48Hmm 6: 48W*96Hmm 7: 72W*72Hmm 8: 96W*48Hmm
9: 96W*96H mm 1680W*160Hmm 80160W*80Hmm
Blank: No alarm 2: 2 alarms 3: 3 alarms
A: No alarm R: With alarm relay output
Signal input
mAV
mAV
mAV
mAV
mAV
TC/RTD/mV/RT
TC/RTD/mV/RT
TC/RTD/mV/RT
TC/RTD/mV/RT
TC/RTD/mV/RT
2
2
2
2
2
2
2
2
Alarm Auxiliary voltage
Transmition output
RS485
SF 8 - I R 2 8 B T - C
Model
1.Electrical parameters
Sample rate
Relay capacity
Power supply AC/DC 100 240V 85-265V
Power consumption
Environment
Storage environment
4 Times/seconds
AC 250V /3A life of rateD load>100,000 times
<6VA
Indoor , temperature: -5 50 no condensation; Humidity:85%RH; Altitude<2000m
-10 60,no condensation
Page02
2.Cable caution
1Please use specified compensation wire in the place of TC input;Please use insulated TC if the measured device is heated metal.
2Please use the cable of lesser resistance in the place of RTD input,and the cable(3 wire) must be no resistance difference,but the total length is within 5m.
3In order to avoid the effect of noise,please put the input dignal away from meter cable,power cable,load cable to wiring.
4
In order to reduce the power cables and the load power cables on the effect of this product,please use noise filter in the place where easy to effect.You must install it
on the grounding of the disk if you use the noise filter,and make the wiring to be shortest between noise filter output side and power connectors.Don`t install fuse and
switch on the wiring of noice filter output side,otherwise it will reduce the effect of noise filter.
5It takes 5s from input power to output.If there is a place with interlocking actions circuit signal,please use timer relay.
6Please use twisted pair with a shield for analog output line,to ensure the reliabilty of signal.
7
Please use twisted pair with a shield for remote RS485 communication cable,and deal with the shield on the host side earth,otherwise it will reduce the effect of noise
filter.
8This product is not the fuse;please set according to rated voltage 250V,rated current 1A if you need;fuse type:relay fuse.
9Please use the suitable screw force and crimp terminal.
The screw terminal sizeM4X8with 7.0X7.0 square base
Recommended tightening torque0.7N.m
Proper cables0.251.65mm single cable/multiple core cable
10Please don`t put the Crimp terminal or bare wire part contact with adjacent connector.
SF□-R28B
Current output
Communication port
Insulation impedance
ESD
Pulse traip anti-interference
Lightning surge
Frequency drop
Dielectric strength
DC 4 20mA load < 500Ω
RS485 port Modbus-RTU procotol
Input,output,power cabinet20MΩ
IEC/EN61000-4-2 Contact ±4KV /Air ±8KV perf.Criteria B
IEC/EN61000-4-4 ±2KV perf.Criteria B
IEC/EN61000-4-5 ±2KV perf.Criteria B
IEC/EN61000-4-29 0% 70% perf.Criteria B
Signal input & output & power AC 500V 1minbelow 60V Low voltage circuit between DC 500V,
1min

Other manuals for SOMMY SF Series

Question and Answer IconNeed help?

Do you have a question about the SOMMY SF Series and is the answer not in the manual?

SOMMY SF Series Specifications

General IconGeneral
Measuring Range0.75 to 300mm (steel)
Measurement Range0.75 to 300mm (steel)
Resolution0.01mm
Display Type4.5 digits LCD with backlight
Power Supply4x1.5V AAA (UM-4) battery
Operating Temperature0 to 40 °C
Dimensions160x68x32mm
Weight208g (not including batteries)

Summary

Model Illustration

Order Model Information

Specifications

Electrical Parameters

Details power supply, consumption, environment, and other electrical specifications.

Signal Parameters

Isolation Diagram

Universal Panel Components

Unit Symbol Comparison

Operation and Menu Navigation

Normal and Shielded Menu Operation

Explains the procedures for navigating normal and shielded menu modes.

Menu Shield Function Flowchart

Uncommon Menu Description

High and Low Limit Display Setting

Linear Signal Self-Calibration

Transmission Range Calibration

Alarm Parameters and Output Logic

Alarm Extension Function

Details alarm handling modes and their effects on output and status.

Dimensions

Connection Drawings

Simple Fault Methods

Communication Protocol

Data Frame Format

Defines the structure of data frames used for Modbus RTU communication.

Abnormal Communication Handling

Describes how to handle and interpret abnormal responses during communication.

Communication Cycle Time

Explains the time requirements for communication cycles between host and meter.

Read Register (0x03)

Details the procedure and address for reading register data.

Write Register (0x10)

Details the procedure and address for writing data to registers.

Address Mapping Table of Meter Parameters