EasyManua.ls Logo

South-Tek Systems N2 Blast FPS-900-RS

Default Icon
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P
The Leader in Nitrogen Generation Technology
FPS-900-RS O&M Manual
Version: 3; 3/2020
Page 17 of 28
See MODBUS addressing table below:
Data Type
Modbus RTU
Address
Units/Status
Read/
Write
BOOL
00012
0=Standby, 1=Running
R
BOOL
00004
1=Good, 0=Alarm
R
BOOL
00015
0=Good, 1=Alarm
R
BOOL
10005
1=Good, 0=Alarm
R
BOOL
10004
1=Good, 0=Alarm
R
BOOL
00029
0=Good, 1=Alarm
R
BOOL
00031
0=Good, 1=Alarm
R
Register
40019
xxxxx.x / hours
R
(2) Analog output (4-20 OUT)
Another useful and optional feature of (FPS) Reliable System units an analog signal
output (4-20 mA) for current readings of different data points as follow:
(i) Ambient temperature4-20 out dEgr.F
(ii) Oxygen content (percent) “4-20 out p.CEnt
(iii) Oxygen content (ppm) 4-20 out trACE
(iv) Supply Pressure 4-20 out prEss
To setup the analog out:
1) Hold the (Set Button) for 5 seconds Passcode Screen will pop up
2) Press the (Set Button) one time to activate data entry, Enter (6557) using the (Up
and Down buttons)
3) Press the (ENT Button) to confirm the entry.
It will bring (Hold Set) Screen, press (NEXT) button to get to the analog output screen 4-20 out”,
Using the (up and down buttons) buttons to change type of sensor, to confirm press (Set button).
To exits menu press (Next button) to get back to main screen “running or standby”.
Note: For analog output standard units (without advanced options) only will offer ambient
temperature signal, check appendix A.

Related product manuals