Southern States CSH-B - User Manual

Default Icon
90 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Type CSH & CSH-B
CSH2 & CSH2-B
Circuit Switcher
Horizontal Circuit Switcher
38kV to 245kV
1200, 1600, 2000 Amps
MANUAL
INSTRUCTION
INSTALLATION &
Appendix A-1 to RFP / Page 1 of 90 pages.

Questions and Answers

  • W
    williamskimAug 8, 2025
    What to do if the motor does not run to close the Southern States Circuit Switcher?
    • J
      Jennifer GuerraAug 8, 2025
      If the motor doesn't run when closing the circuit switcher, it could be due to several reasons. First, the latch check switch might be sensing a discharged shunt trip unit; in this case, hand crank close about five turns while observing the red band indicators on the shunt trip housing. Second, there might be insufficient shunt trip gap in the full open position; adjust the charging bolt to provide the required gap. Finally, the trigger and/or main trip latch in the shunt trip could be sticking; clean and lubricate to ensure the latches reset properly.
  • J
    johnfitzgeraldAug 13, 2025
    Why does the outside pole of my Southern States CSH-B Switch not close?
    • Y
      Yolanda JohnsonAug 13, 2025
      If an outside pole does not close, it could be due to insufficient shunt trip gap in the open position. Adjust the gap using the shunt trip charging bolt.
  • K
    kyle18Aug 18, 2025
    What to do if Southern States Circuit Switcher Opens 1 Second After Trip Initiation?
    • P
      pmcdonaldAug 19, 2025
      If the circuit switcher opens 1 second after trip initiation, it could be due to a trip circuit electrical problem. Check the continuity of the circuit.
  • C
    contrerasrobertAug 23, 2025
    How to fix inconsistent pole simultaneity in Southern States CSH-B?
    • K
      Kathy WilliamsAug 23, 2025
      To address inconsistent pole simultaneity, check the Lever Stop Bole or loose hardware on the rotating insulator, interphase brace channels, and all interphase pipe clamps.
  • M
    Mathew ColeAug 28, 2025
    What to do if there is a delayed opening of one pole in Southern States CSH-B?
    • R
      Russell FoleyAug 28, 2025
      Check trip circuit continuity and trip coil resistance on the delayed pole.
  • M
    Michael JohnsonSep 2, 2025
    How to resolve low SF Pressure 6 in Southern States CSH-B Switch?
    • S
      Shannon VillaSep 2, 2025
      Check for a leak at the gauge end of the interrupter. Otherwise, a replacement unit is recommended.

Summary

Safety Information

General Safety Warnings

Provides essential safety warnings and defines a qualified person for equipment handling.

Product Description

Installation and Adjustment Procedures

Initial Assembly

Step-by-step guide for the initial mounting and assembly of the device.

Mount Pole Assemblies

Instructions for positioning and securing the individual pole units.

Connect Control Piping

Details connecting the interphase and group control pipes for operation.

Final Adjustments and Checks

Covers critical adjustments for shunt trip gap, blade alignment, and indicators.

Disconnect Blade Alignment

Procedures for aligning disconnect blades to terminal pads and contact shoes.

Post-Setup Checklist

A comprehensive checklist to verify successful installation and adjustments.

SF6 Fill Instructions

Step-by-step guide for filling the interrupters with SF6 gas.

Recommended Inspection and Maintenance

Post-Installation Checklist

A checklist for initial verification after installation is complete.

Appendix

Troubleshooting Guide

Lists common problems and their potential solutions for the circuit switcher.