CWC
HWC
HP
OB
PWC
FC
Cooling Water Coil Present
Cooling Water Coil Settings
Switch 1
No Cooling Water Coil Present
Heat Pump Present
Heat Pump Settings
Switch 3
No Heat Pump Present
ON
Potable Water Circulation Settings
Switch 5
OFF
Heating Water Coil Present
Heating Water Coil Settings
Switch 2
No Heating Water Coil Present
Energized in Cooling Mode
Changeover Valve Settings
Switch 4
Energized in Heating Mode
ON
Fan Circulation Settings
Switch 6
OFF
SpacePak G Series Control Dip Switch Settings
Fan On Delay for
Water Coil Heat Demands
Adjustable from
0 - 2 Minutes
SpacePak G Series
Control Variable
Time Delay Settings
0
2
Fan Off Delay for ALL
Heating and Cooling Cycles
Adjustable from
0 - 2 Minutes
0
2
SpacePak G Series Control Indicator LEDs
Power Indicator
The Power indicator will blink to indicate that the control is operational.
F
an Prove Indicator
The Fan Prove indicator will illuminate when there is power to the fan and the optional damper is in the open position.
Note: The Fan Prove Terminal will also energize with 24VAC when the above conditions are met.
F
ault Indicator
Fault Flash Codes:
Float Switch 1 Flash
Anti-Frost Switch 2 Flashes
Fan Prove Fault 3 Flashes
Note: All Flash Codes are latched until power is cycled, even if the fault is cleared. The Float Switch requires power
to be cycled to resume operation.