EasyManua.ls Logo

Speakman GRAVITYFLO SE-4400 - User Manual

Speakman GRAVITYFLO SE-4400
2 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
INSTRUCTIONS FOR MODELS
92-SE-4400-R1
NEED HELP?
TOOLS AND SUPPLIES
IMPORTANT
SE-4400
GRAVITYFLO
®
Portable Eyewash
REQUIRED
ANSI Z358.1 requires that all self-contained eyewash
units shall be visually inspected weekly, unless the
product is placed in environments with extreme
conditions that may affect the form, fit, or function of
the unit (temperature, dirt, etc.). If this is the case, then
the inspection should be conducted more often as the
end user deems necessary. Speakman Company
furnishes a testing record tag (91-0635) with each unit.
On this tag, the date of inspection and the inspectors’
initials should be noted. ANSI Z358.1 specifies that the
height of the spray heads is to be between 33”-45”
from the floor. The SE-4400 weighs approximately 100
lbs when filled. Ensure the mounting surface and
mounting hardware (not supplied) can safely hold a
minimum vertical load of 150 lbs. Be sure to read
instructions thoroughly before beginning installation.
Do not overtighten any connections or damage may
occur. The unit should be full at all times, to achieve the
minimum 15 minute run time as stated by ANSI, in
case of an emergency. Refill the tank to full level after
each activation.
HELPFUL
SAFETY TIPS
MAINTENANCE
Be sure to always wear proper eye protection. Wear
proper skin protect on when cleaning and disinfecting
unit.
Occasional cleaning and disinfection is recommended.
To clean the inside of unit, add 1/4 cup (2 fluid oz.) of
Clorox Liquid Bleach to a full tank of potable water.
Allow the mixture to penetrate for 15 minutes. Drain
tank, and rinse thoroughly several times with potable
water. For further information about Clorox Liquid
Bleach, call toll-free at 1-800-292-2200. Follow
refilling instructions in this manual and place tank back
in service. Should any repair part be required, use only
genuine SPEAKMAN parts for repair or replacement.
See available replacement parts on the final page of
this manual. To order replacement parts, please call
toll-free at 1-800-537-2107
WARRANTY
Additional warranty information can be found at:
www.speakmancompany.com
For additional assistance or service please contact:
SPEAKMAN
®
Company
400 Anchor Mill Road
New Castle, DE 19720
800-537-2107
customerservice@speakmancompany.com
www.speakmancompany.com
Drill necessary holes into mounting surface and
secure Mounting Bracket to surface using
appropriate hardware, being sure to torque to
manufacturer’s specifications.
Select a suitable mounting location for the
SE-4400 capable of supporting 150 lbs. The
location should protect the unit from freezing
and potential scalding conditions. Place
mounting bracket on surface so the top of the
mounting bracket is located between 58
3/8”
-
69
3/8”
from the floor. Making sure the bracket
is level, mark the mounting locations onto the
structure.
Pencil
Level
Drill Drill Bit
Measuring
Tape
Socket
Wrench
Deep Well
Socket
Safety
Glasses
Stud Finder
58-3/8” - 69-3/8”
1483mm - 1762mm
TO FLOOR
NOTE: Mounting hardware not included.
Ensure the mounting surface (wall, etc.) and
mounting hardware can safely hold a minimum
vertical load of 150 lbs.
Question and Answer IconNeed help?

Do you have a question about the Speakman GRAVITYFLO SE-4400 and is the answer not in the manual?

Summary

Tools and Supplies

Required Tools

Lists essential tools like pencil, level, measuring tape, drill, socket wrench for eyewash installation.

Helpful Supplies

Lists optional but recommended items like safety glasses and a stud finder for safe usage.

Important Safety and Compliance Information

ANSI Z358.1 Requirements

Details weekly inspection, spray head height (33-45"), and load capacity (150 lbs) for eyewash units.

Safety Tips

Advises wearing proper eye and skin protection during cleaning and disinfecting procedures.

Maintenance Instructions

Provides guidance on cleaning the unit with a bleach solution and rinsing with potable water.

Warranty Information

Directs users to the Speakman Company website for additional warranty details.

Installation Guide

Select and Mark Mounting Location

Choose a location suitable for 150 lbs, between 58 3/8"-69 3/8" from the floor, and mark bracket positions.

Secure Mounting Bracket

Drill holes and firmly attach the mounting bracket to the surface using appropriate hardware.

Install and Fill Tank

Place the empty tank onto the bracket and fill with potable water to the designated line (approx. 9 gallons).

Secure Fill Cap and Maintenance Tag

Reinstall the fill cap, secure with the seal tie, and attach the maintenance tag to the tank.

Activate Water Flow

Rotate the activation tray downward to begin the flow of water from the eyewash.

Product Specifications and Support

Repair Part Groups

Lists available replacement parts with their respective part numbers and quantities.

Rough-in Dimensions

Provides detailed measurements and diagrams for the unit's physical installation.

Flow Data

Specifies the minimum run time (15 minutes) and flow rate (0.4 gpm) for the eyewash unit.

Need Help?

Contact Speakman Company for additional assistance or service via phone or email.

Speakman GRAVITYFLO SE-4400 Specifications

General IconGeneral
Model NumberSE-4400
Flow Rate20 GPM
ComplianceANSI Z358.1
MountingWall Mount
ADA CompliantYes
Product TypeEmergency Shower
Installation TypeWall Mounted
ActivationPull Handle