Tableros de distribución combinados I-Line™ 80043-808-02 Rev. 02
Anexo 1: Especificaciones—Corriente nominal de cortocircuito adicional 03/2017
40
ESPAÑOL
208Y/120
3P/4W
100,000 LJ
QO (B) 15–70 A 15–125 A
QO (B) VH 15–70 A 15–125 A 15–150 A
QO (B) H 15–100 A
QO (B) GFI 15–30 A
QO (B) EPD 15–60 A
QO (B) AFI 15–20 A
QO (B) CAFI 15–20 A
QO (B) DF 15–20 A
240/120
3P/4W
22,000 QO (B) VH
QO (B) 15–70 A 15–125 A 15–100 A
QO (B) GFI 15–30 A 15–60 A 15–50 A
QO (B) EPD 15–30 A 15–60 A 15–50 A
QO (B) EPE 15–50 A
QO (B) PL 15–30 A 15–60 A
QO (B) AFI 15–20 A
QO (B) CAFI 15–20 A
QO (B) DF 15–20 A
25,000
QD
QO (B) 15–70 A 15–125 A 15–30 A
QO (B) VH 35–150 A
QO (B) PL 15–30 A 15–60 A 15–30 A
QO (B) GFI 15–30 A 15–60 A 15–50 A
QO (B) EPD 15–30 A 15–60 A 15–50 A
QO (B) EPE 15–50 A
QO (B) AFI 15–20 A
QO (B) CAFI 15–20 A
QO (B) DF 15–20 A
ED, FD
QO (B) 15–70 A 15–125 A 15–100 A
QO (B) GFI 15–30 A 15–60 A 15–50 A
QO (B) AFI 15–20 A
QO (B) CAFI 15–20 A
QO (B) DF 15–20 A
Continued on next page
Table 8: Series Connected Breaker Ratings (RMS Symmetrical) (continuación)
Max.
System
Voltage
AC
1, 2
Max.
Short
Circuit
Current
Rating
Square D Brand
Integral or Remote
Main Circuit Breakers
and Remote
Main Fuses
Square D Brand Branch Circuit Breaker
Catalog Designation and Allowable
Ampere Ranges
3, 4, 5, 6
Type 1 Pole 2 Pole 3 Pole
80043-808-01.book Page 40 Wednesday, March 22, 2017 12:31 PM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Square D I-Line and is the answer not in the manual?

Square D I-Line Specifications

General IconGeneral
Bus MaterialAluminum or Copper
Voltage Rating600V AC
Current RatingUp to 1200A
EnclosureNEMA 1
Poles2, 3
Interrupting Rating200 kA (depending on the specific model and installed breakers)