03/2017 Specifications—I-Line Section Ratings
33
ENGLISH
480
100,000
400 A J, T(600 V) HD, HG, HJ, HL, JD, JG, JJ, JL
600 A J, RK5 HJ, HL, JJ, JL
600 A
J, T (600 V) FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ
RK5 FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ
800 A L, T(600V) FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ
1200 A
L FC, KH, KC, LA, LH, LC, MA, MH, MX, NA, PG, PJ
T (600 V) HJ, HL, JJ, JL
1600 A L KC, LC, MA, MH, MX, NA, PG, PJ
2000 A L KC, LC, MH, MG, MJ, MX, NA, PG, PJ
4000 A L HJ, HL, JJ, JL
200,000
200 A RK5 HJ, HL
400 A
J
FA, FH, FC, HJ, HL, JJ, JL, KA, KH, KC, LA, LH, LC,
MA, MH, MX, NA, NC, NX, PG, PJ, PL
T (600 V)
FA, FH, FC, HJ, HL, JJ, JL, KA, KH, KC, LA, LH,
MA, MH, MX, NA, NC, NX
600 A
J
FC, KA, KH, KC, LA, LH, LC, MA, MH, MX, MG,
MJ, NA, NC, NX, PG, PJ, PL
T(600 V) KA, KH, KC, LA, LH, MA, MH, MX, NA, NC, NX
RK5 KC, LA, LH, LC, MA, MH, MX, MG, MJ, NC, NX, PG, PJ
800 A
T(300 V) PG, PJ, PL
T(600 V)
KA, KH, KC, LA, LH, MA, MH, MX, MG, MJ, NA,
NC, NX, PG, PJ, PL
L
KC, LA, LH, LC, MA, MH, MX, NA, NC, NX, PG,
PJ, PL
1200 A L
KC, LC, MA, MH, MX, MG, MJ, NA, NC, NX, PG,
PJ, PL
1600/2000 A L NA, NC, NX
600 100,000
30 A CC HG, JG (Molded Case Switches)
200 A J HD, HG, HJ, HL, JD, JG, JJ, JL
400 A J, T (600 V) HJ, HL, JJ, JL
1
For indicated circuit breakers rated less than this maximum voltage. The indicated short circuit current rating
also applies, but at the voltage rating of the circuit breaker.
Table 6: I-Line Series Connected Fuse Ratings
(RMS Symmetrical) (continued)
Maximum
System
Voltage
AC
1
Maximum
Short Circuit
Current
Rating
Remote Main Fuse
Square D Brand Branch Circuit Breaker
Catalog Designation (2- or 3-Pole)
Unless Otherwise Stated
Max. A Class
80043-808-01.book Page 33 Wednesday, March 22, 2017 12:31 PM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Square D I-Line and is the answer not in the manual?

Square D I-Line Specifications

General IconGeneral
Bus MaterialAluminum or Copper
Voltage Rating600V AC
Current RatingUp to 1200A
EnclosureNEMA 1
Poles2, 3
Interrupting Rating200 kA (depending on the specific model and installed breakers)