EasyManua.ls Logo

Square D I-Line - Page 47

Default Icon
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© 2013–2017 Schneider Electric All Rights Reserved
80043-808-02 Rev. 02 I-Line™ Combo Switchboards
03/2017 Specifications—Lighting Section Ratings
47
ENGLISH
Continued on next page
240 3P/3W or
240 1P/2W
(two pole only)
100,000
FC_ or
KC_24___
QO (B) GFI 15–30 A
FC_ or
KC_34___
DJ 400 A QO (B) H 15–100 A
EJ, FJ QO (B) 15–100 A
LJ
QO (B) VH 15–100 A
QO (B) H 15–100 A
HJ, JJ
QO (B) 15–100 A
QO (B) H 15–100 A
QO (B) VH 35–150 A
QO (B) EPD 15–30 A
QO (B) EPE 15–30 A
125,000 HL, JL
QO (B) 15–100 A
QO (B) H 15–100 A
QO (B) VH 35–150 A
QO (B) EPD 15–30 A
QO (B) EPE 15–30 A
200,000 FI, KI, HR, JR QO (B) 15–100 A
120/240
7
1P/3W
42,000
400 A Max.
Class T3
Fuses
QO (B) VH 15–70 A 15–125 A
65,000
400 A Max.
Class J
Fuses
QO (B) VH 15–70 A 15–150 A
QO (B) AFI 15–20 A
QO (B) CAFI 15–20 A 15–20 A
QO (B) DF 15–20 A
400 A Max.
Class T6
Fuses
QO (B) VH 15–70 A 15–150 A
QO (B) AFI 15–20 A
QO (B) CAFI 15–20 A 15–20 A
QO (B) DF 15–20 A
Continued on next page
Table 8: Series Connected Breaker Ratings (RMS Symmetrical) (continued)
Max.
System
Voltage
AC
1, 2
Max.
Short
Circuit
Current
Rating
Square D Brand
Integral or Remote
Main Circuit Breakers
and Remote
Main Fuses
Square D Brand Branch Circuit Breaker
Catalog Designation and Allowable
Ampere Ranges
3, 4, 5, 6
Type 1 Pole 2 Pole 3 Pole
80043-808-01.book Page 47 Wednesday, March 22, 2017 12:31 PM