Specifications—Lighting Section Ratings 03/2017
48
ENGLISH
120/240
7
1P/3W
100,000
200 A Max.
Class T3
Fuses
QO (B) 15–70 A 15–125 A
QO (B) GFI 15–30 A 15–60 A
QO (B) EPD 15–30 A 15–60 A
QO (B) AFI 15–20 A
QO (B) CAFI 15–20 A 15–20 A
QO (B) DF 15–20 A
200,000
400 A Max.
Class T3
Fuses
QO (B) 15–70 A 15–125 A
QO (B) GFI 15–30 A 15–60 A
QO (B) EPD 15–30 A 15–60 A
208Y/120
3P/4W
200,000
200 A Max.
Class T6, J
Fuses
QO (B) 15–70 A 15–125 A
QO (B) GFI 15–50 A
QO (B) EPD 15–50 A
400 A Max.
Class T3
Fuses
QO (B) 15–70 A 15–125 A 15–100 A
QO (B) GFI 15–30 A 15–60 A 15–50 A
QO (B) EPE 15–50 A
QO (B) EPD 15–30 A 15–60 A 15–50 A
240/120
3P/4W
42,000
400 A Max.
Class T3
Fuses
QO (B) VH 15–30 A 15–125 A
50,000
400 A Max.
Class T3
Fuses
QO (B) VH 15–30 A
65,000
400 A Max.
Class J
Fuses
QO (B) VH 15–70 A 15–125 A
QO (B) EPD 15–50 A
QO (B) EPE 15–50 A
QO (B) AFI 15–20 A
QO (B) CAFI 15–20 A
QO (B) DF 15–20 A
400 A Max.
Class T6
Fuses
QO (B) VH 15–70 A 15–125 A 15–150 A
QO (B) AFI 15–20 A
Continued on next page
Table 8: Series Connected Breaker Ratings (RMS Symmetrical) (continued)
Max.
System
Voltage
AC
1, 2
Max.
Short
Circuit
Current
Rating
Square D Brand
Integral or Remote
Main Circuit Breakers
and Remote
Main Fuses
Square D Brand Branch Circuit Breaker
Catalog Designation and Allowable
Ampere Ranges
3, 4, 5, 6
Type 1 Pole 2 Pole 3 Pole
80043-808-01.book Page 48 Wednesday, March 22, 2017 12:31 PM